Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

INSTALLATION

GENERAL
Installation of the kettle must be accomplished by qualified electrical installation personnel
working to all applicable local and national codes. Improper installation of product could cause
injury or damage.
Gas fired kettles are only to be installed under a ventilation hood in a room which has provisions
for adequate make up air. Observe all clearance requirements to provide proper make-up air flow.
Do not obstruct the flow of combustion and ventilation air. Check rating plate to ensure that kettle
has been equipped to operate with the type of gas available at the installation.
INSTALLATION
The first installation step is to refer to the Specification Sheet for detailed clearance and bolting
requirements. Next, carefully cut open and remove the shipping carton. Remove all supports and
fasteners holding unit to the skid.
Position the kettle in its permanent location, and level the kettle by turning the adjustable flanged
feet. Once positioned and leveled, permanently secure the kettle's flanged feet to the floor using
5/16" lag bolts and floor anchors (supplied by the installer). There are three bolts required to
secure each of the flanged feet.
GAS
ENSURE THE GAS SUPPLY MATCHES THE KETTLE'S REQUIREMENTS AS STATED ON
THE RATING PLATE.
It is recommended that a sediment trap (drip leg) be installed in the gas supply line. If the gas
pressure exceeds 14" water column (3.49 kPa), a pressure regulator must be installed, to provide
a maximum of 14" water column (3.49 kPa) gas pressure to the gas control valve.
Connect the gas line to the manual valve located at the rear of the control box.
Use a gas pipe joint compound which is resistant to L.P. gas. Test all pipe joints for leaks with
soap and water solution. Ensure that the gas pressure regulator is set for the manifold pressure
indicated on the gas rating plate.
The appliance and its individual shut-off valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.45
kPa). The appliance must be isolated from the gas supply piping system by closing its individual
manual shut-off valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.45 kPa).

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis