AC32
Horizontal mounting on the ceiling
Threaded rods, hanging brackets and ceiling mounting
brackets for ceiling mounting are available as accessories,
see accessories pages and separate manuals.

Electrical installation

The installation, which should be preceded by an om-
nipolar switch with a contact separation of at least 3
mm, should only be wired by a competent electrician
and in accordance with the latest edition of IEE wiring
regulations.
The control system is pre-installed in the air curtain.
Unit without heating
Connected via the built-in control board with 1,5 m cord
and plug.
Unit with water heating
Connected via the built-in control board with 1,5 m cord
and plug.
Unit with electrical heating
The electrical installation is made on the top of the unit,
fig.2. Units are intended for permanent installation.
Power supply for heating (400V3N~) are connected to
terminal block in the internal connection boxes. 2-metre
units require dual power supplies. The largest cable dia-
meter for the terminal block is 16 mm². The cable glands
used must meet the protection class requirements. In the
distribution board it is to be indicated that "the air cur-
tains can be supplied from more than one connection".
See wiring diagrams.
Type
Output
[kW]
AC32-10-E08
8
AC32-15-E12
12
AC32-20-E16
16
* Dimensioning of external wiring shall comply with applicable regulations and local
deviations may occur.
Voltage
Minimum
[V]
area
*
[mm
]
2
400V3N~ 2,5
400V3N~ 4
400V3N~ 6
Start-up (E)
When the unit is used for the first time or after a long
period of disuse, smoke or odour may result from dust or
dirt that has collected on the element. This is completely
normal and disappears after a short time.
Connecting the water coil (W)
Operational data:
Max. operating temperature: 110°C
Max. operating pressure: 16 bar
The installation must be carried out by an authorised
installer.
The water coil has copper tubes with aluminium louvers
and is suitable for connection to a closed water heating
system. The heating coil must not be connected to a
mains pressure water system or an open water system.
Note that the unit shall be preceded by a regulating
valve, see VEAB valve kit.
The water coil is connected on top of the unit via steel
pipes with DN20 (3/4'') terminals, external thread. Flex-
ible hoses are available as accessories, see accessories pa-
ges. The connections to the heating coil must be equip-
ped with shut off valves (not included) to allow problem
free removal. Water coil is equipped with a drain valve.
A vent valve should be connected at a high point in the
pipe system. Air valves are not included.
NOTE: Care must be taken when connecting the pipes.
Use a wrench or similar to hold the air curtain connec-
tions to prevent straining of the pipes and subsequent
water leakage during connection to water supply pipe-
work.
Adjustment of the air curtain and air flow
The direction and speed of the air flow should be ad-
justed considering the load on the opening. Pressure
forces affect the air stream and make it bend inwards
into the premises (when the premises are heated and the
outdoor air is cold).
The air stream should therefore be directed outwards to
withstand the load. Generally speaking, the higher the
load, the greater the angle that is needed.
Basic setting fan speed
The fan speed when the door is open is set using the
control. Note that the air flow direction and fan speed
may need fine adjustment depending on the loading of
the door.