INSTALLATION INSTRUCTIONS

Carefully retain all removed parts for later re-assembly.
Unscrew the retaining bolt and washer from the bell gong using a 4mm A/F hexagon key
(not supplied). Remove the solenoid striker and spring from the solenoid cavity at the top of
the case.
Remove the 5 self tapping screws from the bell case lid. The unit allows for up to four cable
entries, two on the top and one either side of the case. The maximum gland size is 20mm.
Drilling points are indicated by the recessed indentations on the surface. Always ensure
that the correct weatherproof gland/s is used.
One proper cable gland for correct IP66 installation is included in the bell delivery (permissible
cable diameter
6-12mm).
The bell case must be mounted on a flat surface with the solenoid striker cavity facing
vertically upwards. Fix the bell case onto the required surface using three 5mm fixing
screws (not supplied).
The bell case has been designed to allow for 'loop in' and 'loop out' cabling requirements.
The DC and AC units are polarity conscious. The DC wires are coloured Red for 'Positive'
and Black for 'Negative'. The AC are coloured Brown for 'Live' and Blue for 'Neutral'. The
high voltage AC units also include an 'Earth' (Ground) Green/Yellow wire.
See picture 1 showing a 230v AC unit.
Once power termination is complete, replace the bell case lid, ensuring the lid gasket is still
correctly fitted, prior to securing with the 5 x self tapping screws. The installer must satisfy
himself that the internal wiring does not foul the weatherproof seal that is formed with the
bell case lid. Failure to achieve a universal seal will invalidate the warranty.
Re-fit the spring and solenoid striker into the solenoid cavity in the case. Replace the 6"
gong directly onto the 6" fixing boss (as indicated on lid) lining up the gong slot with case
boss. Secure with washer and retaining bolt.