Technical Data - GEV FlammEx FMF 3170 Montage

Funk-sende- & empfangsmodul
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

4.
Technical Data
Frequency
433,92 MHz
Power supply
9 V one piece alkaline battery
(not included)
Transmission type
bidirectional
Temperature range 0 -50 °C
Transmission range approx. 25 m in buildings, depending on the
surrounding construction
The device is approved for operation inside the European Community.
GEV GmbH hereby declares that this device (Radio Transmit
and Receive Module FMF 3170) accords with the fundamental
requirements and the other relevant regulations of guideline 1999/5EG.
The full declaration of conformity can be seen under: www.gev.de
Battery and rechargeable battery information
Old batteries may not be disposed of with the unsorted
householwaste. Owners of used batteries are legally
obliged to recycle the batteries and can return them free
of charge to the place of sale. Batteries contain material
which is harmful to the environment and health, and must
therefore be disposed of professionally.
Recycling instructions
This device may not be disposed of with the unsorted
household waste. Owners of old devices are legally
obliged to professionally dispose of this device.
Contact your local council for further information.
22
5.
Fault finding - practical tips
If, when an alarm has been triggered or during testing, a FlammEx radio
smoke detector fails to communicate with other FlammEx radio smoke
detectors, check the following points:
• Check the correct setting of the Coding switch
in the Radio Transmit and Receive Modules in the
other smoke detectors in the system - the codes
must be identical.
• Check that the signal cable (7) is properly connected
between the smoke detector and the Radio Transmit
and Receive Module.
• Check the battery, exchange if necessary.
• Consider the notes under Point 2 of the assembly
instructions section regarding the nature of the sur
rounding buildings etc.
• Reduce the distance between the radio smoke
detectors so that each radio smoke detector in the
same group can exchange radio signals with the
other radio smoke detectors.
• Check the radio connection using another Radio
Transmit and Receive Module and smoke detector.
23