Überprüfung Der Installationsanweisungen; Modbus Register Maps - Sentera Rsmfx-2R Montage- Und Bedienungsanleitung

Multifunktionaler raumtransmitter
Inhaltsverzeichnis
RSMFX-2R
ÜBERPRÜFUNG DER INSTALLATIONSANWEISUNGEN

MODBUS REGISTER MAPS

INPUT REGISTERS
1
Temperature
2
Relative humidity
3
Dew point
4
CO
2
5
Ambient light intensity
6
Active / standby
7—10
Analog output value 1
11
(temperature)
Analog output value 2
12
(relative humidity)
13
Analog output value 3 (CO
)
2
14
Temperature alert flag
15
Relative humidity alert flag
16
CO
alert flag
2
17
Temperature range limit flag unsigned int.
Relative humidity range
18
limit flag
19
CO
range limit flag
2
Humidity / temperature
20
sensor fault
21
CO
Sensor fault
2
22
Ambient light sensor fault
MIW-RSMFX-2R-DE-000 - 05 / 04 / 18
MULTIFUNKTIONALER
RAUMTRANSMITTER
Umgebungslichtsensor
Die gemessene Lichtstärke in Luxes ist verfügbar in Input Register 5. Zusätzlich
kann ein Aktiv und Standby Wert in Holding Register 34 und 35 festgelegt werden.
Input Register 6 gibt an, ob der gemessene Wert unter dem Standby-Wert liegt, über
dem Aktiv Wert oder zwischen beiden Werten:
Wenn die gemessene Lichtstärke niedriger ist als der Standby Wert, zeigt Input
Register 6 "Standby".
Wenn das gemessene Umgebungslicht höher ist als der Active Wert zeigt Input
Register 6 'Active'.
Wenn das gemessene Umgebungslicht sich zwischen dem Active Wert und Stand-
By Wert befindet, zeigt Input Register 6 'Niedrige Intensität'. Wenn diese Funktion
benutzt wird, ist es empfehlenswert die aktiv und Standby Werte in Holding
Register 34 und 35 gemäss dem Umgebungslicht einzustellen.
Nach dem Einschalten der Spannungsversorgung leuchtet eine der LEDs auf gemäss
dem Status der Messgrösse. Ist dies nicht der Fall, überprüfen Sie die Anschlüsse
noch einmal.
Data type
Description
signed int.
Actual temperature level
unsigned int.
Actual relative humidity level
signed int.
Calculated dew point
unsigned int.
Actual CO
level
2
unsigned int.
Measured light intensity
Active or Standby indication according the Active /
Standby light level defined via holding registers 34
unsigned int.
and 35. If the measured light level is between the
two levels, the indication is "0" (Low intensity)
Reserved, return "0"
unsigned int.
Analog output value for temperature (T)
unsigned int.
Analog output value for relative humidity (rH)
unsigned int.
Analog output value for CO
Flag indicates that measured temperature is outside
set alert values. Set to '1' when the measured value
unsigned int.
is outside the temperature alert values defined by
holding registers 20 and 21
Flag indicates that measured relative humidity
is outside set alert values. Set to '1' when the
unsigned int.
measured value is outside the relative humidity alert
values defined by holding registers 22 and 23
Flag indicates that measured CO
alert values. Set to '1' when the measured value is
unsigned int.
outside the CO
range limit values defined by holding
2
registers 24 and 25
Flag indicates that measured temperature is outside
set range limit values. Set to '1' when the measured
value is outside the temperature range limit values
defined by holding registers 14 and 15
Flag indicates that measured relative humidity is
outside set range limit values. Set to '1' when the
unsigned int.
measured value is outside the relative humidity limit
range values defined by holding registers 16 and 17
Flag indicates that measured CO
set range limit values. Set to '1' when the measured
unsigned int.
value is outside the CO
registers 18 and 19
Flag
indicates
if
the
unsigned int.
temperature and humidity sensor is lost
Flag that shows if the communication with the CO
unsigned int.
sensor is lost
Flag that shows if the communication with the
unsigned int.
ambient light sensor is lost
Zurück zu Inhaltsverzeichnis
Data
-300—700
0—1.000
-700—700
0—2.000
0—32.000
0—1.000
0—1.000
0—1.000
2
level is outside set
2
level is outside
2
values defined by holding
2
communication
with
the
2
www.sentera.eu
Values
500 =
1.000 =
200 =
2.000 =
1.000 =
0 =
0—2
1 =
2 =
0 =
1.000 =
0 =
1.000 =
0 =
1.000 =
0 =
Measured temperature is OK
0—1
1 =
Measured temperature is too high/ low
0 =
0—1
1 =
Measured rH is too high/ low
0 =
0—1
1 =
Measured CO
0 =
Temperature range is OK
0—1
1 =
Temperature range is too high/ low
0 =
0—1
1 =
rH range is too high/ low
0 =
0—1
1 =
CO
range is too high/ low
2
0 =
0—1
1 =
0 =
0—1
1 =
0 =
0—1
1 =
50,0 °C
100,0 % rH
20,0 °C
2.000 ppm
1.000 lx
Low light intensity
Active
Standby
0 %
100 %
0 %
100 %
0 %
100 %
Measured rH is OK
Measured CO
is OK
2
is too high/ low
2
rH range is OK
CO
range is OK
2
No
Yes
No
Yes
No
Yes
9 - 11