BMT-DIO4/2
1108831326
Montagehinweis für den Installateur
de
Mounting note for the installer
en
Notice d'installation pour l'installateur
fr
Open Energy Management Equipment 34TZ
de
Nur Kupferleiter verwenden
en
Use copper conductors only
fr
Utiliser uniquement des fils de cuivre
C1| Anschlussbild
Connection diagram
Raccordements
A1 (24 VAC/DC)
N
L
4
3
C1
C1
22
21
24
A1
24 V AC/DC
A1
GND
A2
A2
B+
BUS B+
B+
A-
A-
BUS A-
Jumper below
the faceplate
1
2
C1
C1
12
11
14
A2 (GND)
N
L
4
3
C1
C1
22
21
24
24 V AC/DC
A1
A1
A2
GND
A2
B+
BUS B+
B+
A-
BUS A-
A-
Jumper below
the faceplate
1
2
C1
C1
12
11
14
C2|Prinzipbild
Principle diagram
Schéma de principe
12 N.C.
A1/+24 V
14 N.O.
24 V
11 C
A2 /GND
22 N.C.
BUS B+
24 N.O.
21 C
BUS A-
1
C1
2
C1
3
C1
4
C1
+24 V
GND
J
A1 = C1 = 24 V
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-433
Weitere Dokumentation siehe / additional documentation see / documentation supplémentaire voir www.metz-connect.com
de
DEUTSCH
A| Sicherheitshinweise
GEFAHR
Gefahr bedeutet, dass bei Nichtbeachtung Lebens-
gefahr besteht, schwere Körperverletzungen oder
erhebliche Sachschäden auftreten können.
WARNUNG
Für die Montage, Inbetriebnahme und den Einsatz
des Geräts sind die jeweils länderspezifisch gültigen
Arbeitsschutz-, Unfallverhütungs- und Sicherheits-
bestimmungen einzuhalten und folgendes zu
beachten:
• Facharbeiter oder Installateure werden darauf
hingewiesen, dass sie sich vor der Installation
oder Wartung der Geräte vorschriftsmäßig ent-
laden müssen.
• Montage-, Wartungs- und Installationsarbei-
ten an den Geräten dürfen grundsätzlich nur
durch qualifiziertes Fachpersonal durchgeführt
werden.
• Qualifiziertes Fachpersonal im Sinne dieser
Anleitung sind Personen, die mit den beschrie-
benen Geräten vertraut sind und über eine
ihrer Tätigkeit entsprechenenden Qualifikation
verfügen.
B| Beschreibung
Das BACnet MS/TP Modul mit 4 digitalen Eingängen und 2
Relaisausgängen mit Handbedienebene wurde für dezentrale
Schaltaufgaben entwickelt. Geeignet um z. B. in einem Raum
Lichtschalter und Fensterkontakte aufzunehmen und zwei
Lichtbänder zu schalten oder als Jalousiesteuerung. Ebenfalls
können 2 motorbetriebene Brandschutzklappen gesteuert
werden. Bei starken induktiven Lasten sollten Relaiskontakte
mit einem RC-Glied geschützt werden. Die Eingänge können
als Kontakt- bzw. als Spannungseingänge betrieben werden.
Über einen BACnet-Client können die Eingänge und Ausgänge
über Standard Objekte geschaltet und abgefragt werden. Die
Einstellung der Moduladresse und der Bitrate erfolgt über zwei
Schalter auf der Frontseite. Geeignet zur dezentralen Montage
auf Tragschiene TH35 nach IEC 60715 in Elektroverteilern.
C| Technische Daten
Protokoll
BACnet MS/TP
Adressbereich
00 bis F9
Busschnittstelle
RS485 (Zweidrahtbus)
Übertragungsrate
9600 bis 115200 Bit/s
Betriebsspannung
24 V AC/DC ± 10 % (SELV)
Stromaufnahme
200 mA (AC) / 75 mA (DC)
Einschaltdauer relativ
100 %
Eingänge
4 x digital
Eingang / Spannung
0 – 24 V AC/DC
Eingang / Highsignal
größer 7 V AC/DC
Ausgang / Kontakte
2 x Wechsler (DPDT)
Ausgang / Schaltspannung
250 V AC
Ausgang / Dauerstrom
16 A / Ausgang
Ausgang / Einschaltstrom
80 A, kleiner 20 ms
Anzeige
LED grün, rot, gelb
Abmessungen B x H x T
50 x 69,3 x 60 mm
Gewicht
126 g
Betriebstemperaturbereich
-5 °C bis +55 °C
Lagertemperaturbereich
-20 °C bis +70 °C
Schutzart Gehäuse / Klemmen
IP40 / IP20
Beschreibung
LED Anzeige
vorhandene Betriebsspannung
Grüne LED
Empfangen eines gültigen Kommandos
Grüne LED
vom Master
erlischt kurz
eingestellte Adresse „0"
Rote LED
Kommunikationsfehler, CRC-ERROR
Rote LED
Kommunikationsfehler, Framing-ERROR
Rote LED
unvollständige Frames
Rote LED
Nicht empfangenes Kommando
Rote LED
(bei Ausgangsmodulen)
Eingang / Ausgang aktiv
Gelbe LED
HINWEIS
Zusätzliche Informationen und
Dokumentationen stehen zum Download
unter www.metz-connect.com bereit.
en
ENGLISH
A| Safety instructions
DANGER
Danger means that non-observance may cause
risk of life, grievous bodily harm or heavy material
damage.
WARNING
Follow the applicable country-specific safety at
work rules, the regulations for the prevention of
accidents and safety regulations when mounting,
bringing into service and using the device and
observe the following:
• Technicians and/or installers are informed that
they have to electrically discharge themselves as
prescribed before installation or maintenance of
the devices.
• Only qualified personnel is allowed to do moun-
ting, maintenance and installation work on the
devices.
• Qualified personnel in the sende of these inst-
ructions are persons who are well versed in the
use and installation of such devices and who
possess the necessary qualification for their job.
B| Description
The BACnet MS/TP module with 4 digital inputs and 2 relay
outputs with manual control was developed for decentralized
switching tasks. It is suitable for accommodating, for example,
light switches and window contacts in a room, switching two
light strips or controlling louvers. It can also be used to control
2 motorized fire dampers. With strong inductive loads, we
recommend protecting the relay contacts with an RC element.
The inputs can be used as contact or voltage inputs. The
inputs and outputs can be switched and scanned by means of
standard objects via a BACnet client. The module address and
the baud rate are set by means of two address switches on the
front. Suitable for decentralized mounting on DIN TH35 rail
according to IEC 60715 in electrical distribution cabinets.
C| Technical Data
Protocol
BACnet MS/TP
Addressing range
00 to F9
Bus interface
RS485 (two-wire bus)
Transmission rate
9600 to 115200 baud
Operating voltage
24 V AC/DC ± 10 % (SELV)
Current consumption
200 mA (AC) / 75 mA (DC)
Relative duty cycle
100 %
Inputs
4 x digital
Input / voltage
0 – 24 V AC/DC
Input / high signal
more than 7 V AC/DC
Output / contacts
2 changeover contacts
(DPDT)
Output / switching voltage
250 V AC
Output / continuous current
16 A / output
Output / switch-on current
80 A (less than 20 ms)
Display
Green, red and yellow LED
Dimensions (W x H x D)
50 x 69.3 x 60 mm
Weight
126 g
Operating temperature range
-5 °C to +55 °C
Storage temperature range
-20 °C to +70 °C
Ingress protection
for housing / terminal block
IP40 / IP20
Description
LED display
Operating voltage is present
Green LED
Reception of a valid command
Green LED turns
from the Master
off briefly
Address setting "0"
Red LED
Communication error, CRC ERROR
Red LED
Communication error, framing ERROR
Red LED
Uncomplete frames
Red LED
Not received command
Red LED
(for output modules)
Input / Output active
Yellow LED
NOTE
More detailed informations and
documentations are available as download
at www.metz-connect.com
fr
FRANÇAIS
A| Avis de sécurité
DANGER
Danger signifie que de la non observation des
consignes peut entraîner un risque mortel ou des
dommages matériels importants.
AVERTISSEMENT
Pour le montage, la mise en service et l'utilisation
de l'appareil il faut respecter les règlements en
vigueur selon le pays concernant la protection au
travail, la prévention des accidents et la sécurité et
de respecter aussi les avis suivants :
• Des travailleur qualifiés ou installateurs sont
avertis qui'il est nécessaire de se décharger
correctement de l'électricité avant d'installer ou
d'entretenir l'appareil.
• Seul du personnel qualifié est autorisé à effectu-
er le montage et l'installation, voir paragraphe
personnel qualifié.
• Du personnel qualifié au sens de ces instructions
sont des personnes qui sont familiers avec les
appareils décrits et dont le qualifications pro-
fessionnelles sont en rapport avec leur travail.
B| Description
Le module BACnet MS/TP avec 4 entrées numériques et
2 sorties de relais avec fonction de commande manuelle a été
conçu pour les tâches de commutation décentralisées. Convi-
ent par ex. pour intégrer des commutateurs d'éclairage et des
contacts de fenêtre et pour commuter deux lignes continues
ou comme commande de persiennes dans une pièce. Il permet
également de commander 2 clapets coupe-feu motorisés. En
cas de fortes charges inductives, il est recommandé de proté-
ger les contacts de relais par un circuit RC. Les entrées peuvent
être utilisées comme entrées de contact ou de tension. Un
client BACnet permet de commuter et d'interroger les entrées
et les sorties via des objets standards. Le réglage de l'adresse
du module et de la vitesse de transmission s'effectue par deux
interrupteurs situés sur la face avant. Convient au montage
décentralisé sur rail DIN TH35 selon IEC 60715 dans des répar-
titeurs électriques.
C| Données techniques
Protocole
BACnet MS/TP
Plage d'adresses
de 00 à F9
Interface bus
RS485 (bus à deux fils)
Vitesse de transmission
de 9 600 à 115 200 bd
Tension de service
24 V CA/CC ± 10 % (SELV)
Consommation électrique
200 mA (CA) / 75 mA (CC)
Taux de marche relatif
100 %
Entrées
4, numériques
Entrée / tension
0 – 24 V CA/CC
Entrée / signal haut
supérieur à 7 V CA/CC
Sortie / contacts
2, inverseurs (DPDT)
Sortie / tension de commutation 250 V CA
Sortie / courant continu
16 A / sortie
Sortie / courant de démarrage
80 A, inférieur à 20 ms
Affichage
DEL verte, rouge, jaune
Dimensions L x H x P
50 x 69,3 x 60 mm
Poids
126 g
Plage des températures
de service
de -5 °C à +55 °C
Plage des températures
de stockage
de -20 °C à +70 °C
Indice de protection
boîtier/ bornes
IP40 / IP20
Description
Affichage
par DEL
Tension d'alimentation présente
DEL verte
Récéption d'une commande valable du
La DEL verte
Maître (Master)
s'éteint
brièvement
Adresse réglée « 0 »
DEL rouge
Erreur de communication, CRC ERROR
DEL rouge
Erreur de communication,
DEL rouge
Framing ERROR
Trames (Frames) incomplèts
DEL rouge
Commande non reçue
DEL rouge
(pour les modules de sortie)
Entrée / Sortie active
DEL jaune
NOTICE
Informations et documentations
supplémentaires sont disponibles pour
téléchargement à www.metz-connect.com.