14. EMC

EMC Immunity
Electrostatic discharge
Electromagnetic RF field
Fast transients (Burst)
Surge voltage on input
Surge voltage on output
Surge voltage on Signals
Conducted disturbance
Mains voltage dips
Voltage interruptions
Powerful transients
Criterions:
A:
Power supply shows normal operation behavior within the defined limits.
B:
Temporary loss of function or performance during the tests - self recoverable.
EMC Emission
Conducted emission
input lines
Conducted emission
output lines 2)
Radiated emission
Harmonic input current
Voltage fluctuations, flicker
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
Switching Frequencies
PFC converter
Main converter
Auxiliary converter
Revision 1, status Nov. 2017
According to EN 61204-3
EN 61000-4-2
Contact discharge
Air discharge
EN 61000-4-3
80MHz - 6GHz
EN 61000-4-4
Input lines
Output lines
DC-OK signal (coupling clamp)
EN 61000-4-5
T.b.d.
EN 61000-4-5
T.b.d.
EN 61000-4-5
T.b.d.
EN 61000-4-6
0.15-80MHz
0% of 380Vac
EN 61000-4-11
40% of 380Vac
70% of 380Vac
0% of 480Vac
40% of 480Vac
70% of 480Vac
EN 61000-4-11
0% of 380Vac (=0V)
VDE 0160
Over entire load range
According to EN 61204-3
EN 55011, EN 55015, EN 55022, FCC Part 15,
CISPR 11, CISPR 22
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
EN 55011, EN 55022
EN 61000-3-2
EN 61000-3-3
25-120kHz
100 to 130kHz
30kHz
8kV
8kV
T.b.d.
4kV
2kV
2kV
2kV
4kV
1kV
2kV
1kV
T.b.d.
0Vac, 20ms
152Vac, 200ms
266Vac, 500ms
0Vac, 20ms
192Vac, 200ms
336Vac, 500ms
5000ms
1584V, 1.3ms
Class A
Not required, not considered to be a DC-mains
Class A
Class A fulfilled
Fulfilled, tested with constant current loads, non
pulsing
Input voltage dependent
Output load dependent
Fixed frequency
English.
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion B
Criterion B
Criterion A
Criterion B
Criterion A
Criterion B
Criterion A