GB: • The top part is dismounted by loosening the two black
screws.
• The energy meter's M-Bus wires are mounted in terminals
24 and 25 of RF M-Bus Converter II, see picture.
• If an external antenna type Triangle is required, it is also
connected. Please remember to check the selector switch.
• The mains supply is connected in the left side of RF M-
Bus Converter II. The mains supply must be switched off
before installation.
• The top part is remounted and the mains supply is
reestablished.
• RF M-Bus Converter II starts communicating with the
connected energy meter.
If a communication error occurs, light-emitting diodes 1
and 2 will flash for some seconds.
Please note: The duration of the initialization phase can
be up to one minute depending on the energy meter
make.
After successful communication with the energy meter RF
M-Bus Converter II automatically starts creating a local list.
The local list includes information of up to 70 other radio
units (radio modules/RadioRouter modules/RF Router/RF
Concentrator).