Example:
PV1 = 6000Wp / PV2 = 3400Wp
Specification:
This should be variably reduced to 70% of the maximum PV generator power.
Calculation of the minimum possible power limit:
PV2 : (PV1 + PV2) = 3400Wp : (6000Wp + 3400Wp) = 0,36
Minimum possible possible power limit= 36% of the max. PV generator power of 9400W (DC)
Result:
The energy meter is connected to inverter 1. Under the „Dyn. feed in control" menu item in the
inverter, a value of 6580W (= (PV1 + PV2) * 0.7) is set.
If necessary, inverter 1 can reduce its output power to ensure that the maximum permissible value
of 6580W at the grid transfer point is not exceeded. The specified power limiting to 70% of the
maximum PV generator power is thus adhered to.