Installation and
Operation Instructions
Electronic
Clock Thermostat
easy 3s
Warning!
This unit must not be opened and installed except by autho-
rized persons and in compliance with the circuit diagram pro-
vided inside the cover. It is mandatory in all work on the unit to
observe the current safety regulations.
In order to classify for protection class II it is necessary to take
adequate installation measures.
This separately mounted unit is designed for temperature con-
trol exclusively in dry and closed rooms with standard environ-
ment. The unit features radio-interference suppression in
compliance with VDE 0875 T. 14 and EN 55014, res -
pectively and works according to operating principle 1 C
(EN 60730).
1. Applications
The easy 3s electronic clock thermostat is designed for
room temperature control in conjunction with:
heating systems, e.g. hot-water heaters, convector hea-
ters or floor heating
electric convector heaters, ceiling and storage heating
night-storage heaters
chillers
circulation pumps
burners and boilers
heat pumps, etc.
airconditioning applications (cooling only)
Features
very simple operation
comfort and setback temperature adjustable
5 operating modes (by rotary switch) for:
➩ permanent comfort temperature (5...30°C)
➩ permanent setback temperature (5...30°C)
➩ clock mode (automatic)
➩ frost protection (5°C fixed)
➩ OFF
Indicator lamps for: ➩ heat demand
➩ setback mode
available with daily or weekly timer
control by phone remote switch possible
output signal PWM or ON/OFF regulation (adjustable via
jumper)
relay output, 1 x changeover contact
remote sensor optional
emergency operation at sensor failure
hinged cover
new design 2000
2. Function description
The clock thermostat is designed to control the room tem-
perature.
In the automatic mode, a changeover is effected between
comfort and setback mode by the built in timer.
Optionally remote sensor can be used instead of built-in
sensor.
In setback mode the green indicator lamp lights up.
If room temperature drops below set value, heating will
start, the red indicator lamp will light up.
Indicator lamps
Red
indicates when controller demands heat,
Green indicates when setback mode is activated.
Red
flashing for failure. Operating voltage to be swit-
ched OFF and ON again.
Controller heat demand at PWM
If room temperature drops below the set value, heating
mode will start. The controller output is in the form of pul-
ses of varying length (PWM). The length of the pulses
depends on the difference between set and actual room
temperature.
The sum of pulse and pause times can be selected with
J 4 (between 10 or 25 min.).
If there are large temperature differences, the controller
will switch ON or OFF permanent, e.g. when changing
over to temperature setback mode. PWM should only be
used for current ≤ 10A
On
Off
Temperature
set temperature
10/25 min
Fig. 1: Characteristic of impulse pause ratio de pen ding on temperature
Cycle time setting
For inert applications (e.g. burners) we recommend the
long cycle time.
For quick applications (e.g. electric direct heaters) we re -
com mend the short cycle time.
Plug-in jumper J4
Time
(right side of board)
Double-pole jumper
25 min
connection
(as-delivered condition)
Single-pole jumper
10 min
connection
Heat demand of the controller at ON/OFF regulation
When room temperature drops below set temperature the
output will be switched on, whereas it will be switched off,
when set value is exceeded.
ON
OFF
Hysteresis
set temperature
Fig. 2: ON/OFF regulation
Plug-in jumper J3
Regulation
(right side of board)
Double-pole jumper
ON/OFF
connection
Single-pole jumper
PWM
connection
(as delivered condition)
Phone remote switch
(only available at special variants)
Via an external phone switching device the conroller can
be put into mode of comfort or setback temperature. As
long as contact (terminal 19) is closed, the comfort tem-
perature will be "used". This function ist activated in the
modes 2 automatic, Ñ setback temperature permanent
and P Frostprotection.
3. Installation
The controller should be arranged in a place within the
room which:
• is easily accessible for operation
• is free from curtains, cupboards, shelves, etc.
• enables free air circulation
• is free from direct sun radiation
• is free from draughts (e.g. opening of windows and doors)
• is not affected directly by the source of heat
• is not located on an external wall
• is located approx. 1,5 m above floor level
Mounting directly on conduit box or with adapter
frame ARA easy.
Electric connection
Warning! Disconnect electric circuit from supply.
Proceed as follows:
• pull off temperature setting knob
• push retaining hook outwards using screwdriver
• remove housing cover
• make connection in compliance with wiring diagram (see
housing cover).
• watch notes
Remote sensor
Having connected the remote sensor, the integral sensing
component will be switched off automatically.
The sensor cable is extendable up to a length of max.
50 m. Please use a two-core 230 V cable with a cross sec-
2
tion of 1.5 mm
.
The sensor cable (F 193 720) should be installed into a
protection tube (pocket). This facilitates later replacement.
In case of failure (break or short-circuit) the controller swit-
ches into emergency operation:
at PWM:
30% heating capacitiy
at ON/OFF: Relay OFF
Warning! Sensor cables carry operating voltage.
4. Technical data
Temperature setting range:
comfort temperature
5...30°C
setback temperature
5...30°C
frost protection
approx. 5°C fixed
Regulation
proportional controller
(due to PWM quasi-continuous, see Fig.1)
Cycle period
adjustable 10 or 25 min.
(sum of PWM ON and OFF times)
Proportional band
1,5 K
~0,5 K, ≤ 10 A see Fig. 2
Hysteresis
~0,5K at 16 A and use with remote sensor
~2,5 K, at 16 A without remote sensor
ON/OFF regulation
adjustable via jumper
Output
relay, 1 volt-free* changeover contact
10 mA...16 A cos ϕ = 1
Switching current
max. 4 A cos ϕ = 0,6
max. 10 electro-thermal actuators
Switching voltage
24...250 V AC
Mode selector switch
comfort / automatic / setback /
frost protection / OFF
Phone remote switch
Input for 230 V AC (via an external
(as variant)
phone switching device)
Indicator lamp:
red
controller demands heat
green setback mode
Temperature sensor:
internal
Remote sensor
type F 190 021 (wall mounting)
type F 193 720 length 4 m
both extendable up to 50 m
Sensor characteristics
42 kΩ at 20 °C
26 kΩ at 30 °C
Range limitation
inside setting knob
Clock:
accuracy
< 10 min./year
switching time setting every 15 min. with daily timer
every hour with weekly timer
temperature
power reserve
approx. 100 h
Protection class of housingIP 30
Degree of protection
II (see Warning 1)
Ambient temperature
–10...40 °C, without condensation
Storage temperature
–25...65°C
Dimensions
160 x 80 x 36 mm
Weight
approx. 220 g
* The volt-free contact of this mains-operated unit does not ensure
the requirement for the use of safety extra-low voltage (SELV).
For units with 230 V supply voltage
Type
easy 3st with daily timer
easy 3sw with weekly timer
Article-Nr. easy 3st
517 2701 51 100
easy 3sw
517 2702 51 100
Operating voltage
195...253 V AC 50/60 Hz
Power consumption
< 1,5 W
For units with low voltage output
Type
easy 3st 1mA with daily timer
easy 3sw 1mA with weekly timer
Article No. easy 3st 1mA
517 2711 51 100
easy 3sw 1mA 517 2712 51 100
Operating voltage
195...253V AC 50/60Hz
Switching current
>1 mA, >1V or max. 10(4) A AC
Power consumption
< 1,5 W
5. Wiring diagram
Symbol explanation
U Heaing          P Cooling         
Remote sensor
Phone remote switch
Note
For heating applications
• connect n/c actuators to terminal 2.
• connect n/o actuators to terminal 3.
For cooling applications
• connect n/c actuators to terminal 3
• connect n/o actuators to terminal 2
• To use the red lamp as indicator for "cooling ON",
connect n/o actuators to terminal 2
• When mode selector switch is in OFF position
and n/o actuators will be closed logically.
6. Operation
Temperature setting
1
Comfort temperature (daytime temperature)
is set by means of externally visible seting knob (1)
2
Setback temperature (night temperature)
is set by means of adjustment knob (2) beneath cover.
Time setting
3
by putting one finger on dial (3) and turning in any
direction, you can set the time.
4
Arrow (4) points to the selected time.
Switching time setting
5
Bring movable tappets (5) into required position using
a pointed object.
Outer ring = comfort temperature
Inner ring = setback temperature
6
Mode selector switch (6) – externally
É Comfort temperature, permanent
2 Automatic mode, time-controlled changeover
between comfort and setback temperature
Ñ
Setback temperature, permanent
P Frost protection, permanent (5°C)
OFF, there is no control activity. The controller itself is
not disconnected from operating voltage.
3
4
5
6
21
2
1
Batteries
In compliance with the EU Directive
2006/66/EC, the button cell battery located
on the printed circuit board inside this
product, can be removed at the end of the
product life, by professional personnel only.
n/c

Werbung

loading

Inhaltszusammenfassung für Eberle easy 3s

  • Seite 1 2 4. Technical data • When mode selector switch is in OFF position The easy 3s electronic clock thermostat is designed for Temperature setting range: and n/o actuators will be closed logically. room temperature control in conjunction with: comfort temperature 5…30°C...
  • Seite 2 : avec MIL : 30 % Heizen Le thermostat à horloge électronique easy 3s peut être utili- régulation à 2 points : relais déconnecté sé pour régler la température des pièces en association Attention ! Les câbles du capteur sont sous tension.
  • Seite 3 Fernfühler 1. Anwendungsgebiete ☎ Absenktemperatur 5…30°C Telefonfernschalter Frostschutz ca. 5°C fest Der elektronische Uhrenthermostat easy 3s kann verwen- Sollwert Temperatur Regelverfahren Proportional-Regler (durch det werden zur Raumtemperaturregelung in Verbindung mit: 6. Bedienung PWM stetigähnlich s. Bild 1) Heizanlagen wie: Warmwasser-, Konvektor- oder •...