• The heaters should always be installed horizontally only using the mounting brackets
provided. This ensures correct positioning and adequate clearance.
• A minimum air gap of 150 mm should always be allowed between the top of the heater
and a ceiling or roof. The appliance should be 600 mm far from the walls (fig.1).
• A safety distance of not less than 1000 mm should always be left in front of the Casa-
Therm heaters or too near.
• This unit should be mounted at a minimum of 1500 mm above ground level (fig.1). If
installed in a toilet, the height should be 2250 mm in zone 1 and zone 2; in zone 3 the
minimum above ground level is 1500 mm, according with the rules of each Country.
• Be sure that the heater is not facing the ceiling or inflammable substances.
• The appliance must not be located neither directly below, nor in front of a socket-outlet.
• The heater must be installed so as to prevent that the switches can be touched from
those who are in the shower.
• Ensure that there is no possibility of inflammable material, combustible material or cur-
tains coming into contact with the heater, or lie near the heater.
• Heaters should not be installed in areas where hazardous vapours may be present. De-
fined in BS5345.
• The heaters are fitted with safety guards. These are intended only to stop large objects
from hitting the emitters. On no account should the heater be operated with the guard
removed.
• For consumer use the heaters are fitted with high temperaure silicone rubber flexible
cable (H05 RN-F) conforming to BS 6500.
• The models for professional use, that are marked with a "P" in the code, do not have the
power cord and the switch. For professional installation, cabling of the same specification
should be selected.
• The product is in class I and IP55, wich is the protection rate for the units to be used even
outdoor. For keeping the protection rate of the appliance, the connection of the appliance
with the power supply must be done by means of a minimum IP55 system, as per the
standards HD 384 CENELEC for Europe, or international IEC 60346-7-708 1988, and the
standard AS/NZS 3000 (Australian wiring rules).
• Means for disconnection must be incorporated in the fixed wiring in accordance with the
wiring rules.
• Avoid to touch the metal parts.
3. LOCATION
The range of CasaTherm heaters has been designed to provide flexibility in positioning.
Three different options can be chosen:
• Wall mounting using the support provided (included). Before drilling holes into the
wall for fixing the rawlplugs, ensure that it is solid and that there are no electrical cables
or suchlike behind. Using a 5 mm drill bit, drill 2 holes into the wall and fix the support
using the supplied rawlplugs. In doing so, ensure that the slots in the support are located
at its lower end (Fig. 2 and Fig. 2-A), and the arrow on the label is turned up (Fig. 5).
• Ceiling mounting with chains. Before drilling holes, ensure that the area of ceiling on
which it is intended to fix the appliance is solid and that there are no electrical cables or
suchlike behind. Fit the chains to the appliance as shown in Fig. 3.
11