7.0

Technical Data

(at 23° C % 5° C, max. 75 % rel. humidity)
Display:
Range Selection:
Auto-Power-Off:
Overload display:
Measuring rate:
Clamp opening:
Overvoltage Categorie:
Pollution degree:
Height above MSL.:
Battery display:
Power supply:
Current Consumtion:
Operation temperature: -10° C ... 50° C at less then 85% rel. H.
Storage temperature:
Dimension:
Weight:
Voltage AC 50/60 Hz
Range
5 V...600 V
Current AC 50/60 Hz (mA and A); Crest Factor <4
Range
0,50...60 mA
60...99,99 mA
100...600 mA
0,050...3,00 A
3,00...30,00 A
30,00...50,00 A
Overvoltageprotection: 600 A AC
Harmonics in mA, A Range (%)
Spezifiziert ab 100mA 50/60Hz (mA Range) oder ab 1A 50/60Hz
(A Range)
Range
1...10
11...20
21...50
51...99
4+2+2, LCD incl. functions and symbols
automatic
approx. 30 min.
OL
2 measurements/sec. (LCD)
ca. 30 mm (1/2 inch)
CAT II, 600 V / CAT III, 300 V
2
up to 2000 m
at low battery
Batterie 2 x 1,5 V IEC LR6 (alkaline)
approx. 10 mA
-20° C ... 60° C at less then 75% rel. H.
210 x 6235,6 x 35,6 mm
approx. 200 g
Resolution
0,1 V
Resolution
0,01 mA
0,01 mA
0,1 mA
0,001 A
0,01 A
0,01 A
Resolution
0,1 %
0,1 %
0,1 %
0,1 %
Accuracy
± 0,5 % ± 5 D
Accuracy
± 0,5 % rdg. +5 D
± 0,5 % rdg. +50 D
± 0,5 % rdg. +5 D
± 0,5 % rdg. +5 D
± 0,5 % rdg. +5 D
± 1,0 % rdg. +5 D
Accuracy
± 1 % rdg. ± 1%
± 5 % rdg. ± 1%
± 15 % rdg. ± 1%
± 35 % rdg. ± 1%