Safety instructions

For skilled electricians and instructed personnel in
accordance with national legislation, including the
relevant standards and, where applicable, in acc.
with IEC 60079-14 on electrical apparatus for
explosive atmospheres.
❒ The light fitting must not be operated in zone 0
or 20 hazardous areas!
❒ The technical data indicated on the light
fitting are to be observed!
❒ The requirements of the IEC/EN 60079-31
regarding excessive dust deposits and
temperature to be considered from the user.
❒ Changes of the design and modifications to
the light fitting are not permitted!
❒ The light fitting shall be operated as in-
tended and only in undamaged and perfect
condition!
❒ Only genuine CEAG/Cooper Crouse-Hinds
GmbH (CCH) spare parts may be used for
replacement!
❒ Repairs that affect the explosion protection
(see national standard), may only be carried
out by CEAG/CCH or a qualified "electrician"!
❒ Do not keep these operating instructions
inside the light fitting during operation!
The national safety rules and regulations for
prevention of accidents and the following safety
instructions which are marked with an (
these operating instruction, will have to be
observed!
2.

Conformity with standards

The light fitting is suitable for use in zone 1, 2 and
21, 22 hazardous areas acc. to EN/IEC 60079-10-1
and EN/IEC 60079-10-2.
It has been designed, manufactured and tested
according to the state of the art and according to
EN ISO 9001:2008 and EN ISO/IEC 80079-34.
The light fitting is conform to the standards specified
in the EC-Declaration of conformity, enclosed
separately.
3.

Technical data

ATEX type examination certificate
BVS 09 ATEX E 029
Marking acc. to 94/9/EG and standard:
EN 60079-0:
ta
+ 40 °C:
II 2 G Ex e ib mb IIC T6 Gb
max
ta
+ 50 °C:
II 2 G Ex e ib mb IIC T5 Gb
max
II 2 D Ex tb IIIC T80°C Db IP66
IECE X type examination certificate:
IECE X BVS 13.0017
Category of application:
IEC 60079-0:
ta
+ 40 °C: Ex e ib mb IIC T6 Gb
max
ta
+ 50 °C: Ex e ib mb IIC T5 Gb
max
Ex tb IIIC T80°C Db IP66
Address
Address
switch 1
switch 2
0
0
0
1
0
2
...
...
1
0
1
1
...
...
...
...
2
0
2
1
...
...
9
9
Fig. 4 Addressing
4 4 4 4 4
Cooper Crouse-Hinds GmbH
Rated voltage AC:
EXIT 24 V
EXIT
EXIT CG-S
Rated voltage DC:
EXIT 24 V
EXIT
EXIT CG-S
Rated frequency
Rated current
110 V AC/DC:
230 V AC/DC:
Insulation class
to EN 60 598:
Degree of protection
accd. EN 60529
Operation temperature
(Deviating temperatures possible with special versions.)
Storage temperature
in original packing:
Weight:
Supply terminal clamping capacity
2 x per terminal:
Ex-e cable entry
standard version:
metal thread:
Test torque for M 20 x 1.5 Ex-e
cable entry:
Test torque for pressure
screw:
(for sealing off the cable or the blanking plug)
max. permissable tolerances accd. EN 60079-0
4. Installation EXIT
) in
The respective national regulations as well as
the general rules of engineering which apply to the
installation and operation of explosion protected
apparatus will have to be observed!
Transport and storage of the luminaire is permitted
in original packing and specified position only!
4.1 Opening and closing the light fitting
❒ Unscrew the four screws of the cover.
❒ The cover can be opened to the molded hinges.
For ease of installation, the cover can be removed
out of the hinges. If putting down take care to
prevent scratches on the silk screen cover.
4.2 Installation of the fitting
The luminaire shall be fitted by using the four
mounting clips with suitable fixing screws
(Ø 5 mm, fig. 1) onto a suitable surface.
4.3 Mains connection
Open the cover as described.
Pass the cable (5.5 to 13 mm) through the certified
Ex cable entry M 20 x 1,5. Use both sealing inserts
for cables from 5.5 to 8 mm, and the outer sealing
insert only for cables from 8 to 13 mm. Pay attention
to the proper fit of the remaining sealing insert in the
certified cable gland.
In case of unused cable entries, remove their
protective cover and close the entries with a blanking
plug (torque of 2.5 Nm). When closing the gland with
a blanking plug, always use both sealing inserts!
When metal cable entries are used, the protective
caps of the unused entries are to be removed and
the entries to be closed with certified Ex blanking
plugs!
Luminaire
Attention!
address
Only fix laid cable may be used for connection!
Monitoring off
If cable glands from other manufacturer are used
1
the instructions regarding strain relief and clamping
2
capacity must be observed!
...
Connect the conductors to the terminals L, N and PE
10
in accordance with the terminal marking (see fig. 2).
11
Remont the LED-printed board into the housing.
...
Take care not to pinch any conductors. Install the
...
protective cover with the four screws. Tighten the
20
screws only hand-tight!
not permissable
not permissable
5. Monitoring (only EXIT CG-S)
non-permissible
The CG-S module monitors and indicates to the connected
110 V - 277 V*
CEAG emergency supply system the operation of the supply
220 V - 254 V*
unit circuit and the function of min. 50 % of the installed
LEDs.
12 - 24 V DC ± 20%
The CG-S module allows single monitoring of these
110 V - 250 V *
luminaires in CEAG emergency lighting systems. The
195 V - 250 V *
switching mode (maintained/non-maintained and switched
50 - 60 Hz
emergency luminaires) is freely programmable and mixed
operation up to 20 addresses in a single circuit is possible.
0.05 A
0.025 A
5.1 Addressing
I
Before fitting the cover, the addressing of the individual
luminaires is to be carried out. The desired address (fig.4, 1
IP 66
- 20) is set on the address switch by means of a suitable
-20 °C to +40°C/+50°C
screw driver (Arrowhead to No., fig. 3). If the luminaire
should not be monitored the code 0/0 has to be selected.
The standing luminaire EXIT and is not equipped with
-40°C to +60°C
monitoring circuit and can not be addressed.
approx. 2.2 kg

6. Taking into operation

3 x 2.5 mm²
M20x1,5 for cable
functioning and installation in compliance with these
Ø 5,5 to 13 mm
operating instructions and other applicable regulations!
M20x1.5
Only carry out insulation measurements between PE and
3.75 Nm
the external conductor L as well as between PE and N.
– measuring voltage: max. 1 kV AC/DC
2.5 Nm
– measuring current:
out between L and N, since that would destroy the
electronics (mains input fuse in the unit).

7. Maintenance

maintenance, servicing and test of apparatus for explosive
atmospheres e.g IEC/EN 60079-17 as well as the general
rules of engineering!
7.1 Servicing
When servicing, in particular those components that affect
the explosion protection, will have to be checked, e. g.:
❒ Housing and protective bowl for any cracks or damages.
❒ Gaskets for their perfect condition.
❒ Terminals and blanking plugs for their firm fit.
❒ Because of the risk of an electrostatic charge, the light
fitting shall only be cleaned with a damp, non-fibrous
cloth or sponge!
Only use customary household washing-up liquid diluted
in water as specified! The water temperature may be
max. 50°C.
After that, rinse with clear water to prevent the risk of
tension cracks in the protective bowl!
7.2 Repair
Prior to replacing or removing any components, observe
the following:
Cut the apparatus off the voltage before opening it or
carrying out repairs! Only use certified genuine CEAG/
CCH spare parts! (See CEAG/CCH spare parts list).
Subject to alteration or supplement of this
product series.
Regarding waste disposal, observe the relevant national
regulations! The plastic materials are marked with material
identifications.
Prior to operation, check the light fitting for its proper
max. 10 mA
Mind: There must no insulation measurement be carried
Observe the national regulations applicable to the