Operating Instructions
Selection
Description
"deactivate"
Default set-up – function disabled
"active"
Function as described above. The selected operating mode ("open" or "closes" see chapter 7.6.) is
kept even if the trigger is not available. The re-closing lockout function is reset by actuating the DIP
switch LF1 or LF2 (ON-OFF-ON or OFF-ON-OFF) or a short disruption of the power supply. In
case of a detected error in parallel the limit value contact turns to the selected alarm state (e.g.
"opens if value > limit value" the contact opens)
7.9 Start-up delay
The start-up delay overrides an alarm, if the setting "closes if value < limit value" or "opens
if value < limit value" is selected. The function allows to start-up machines and engines
without an alarm. Setting range: 0...999sec.
The activated function is triggered by the first slope of the input signal. The start-up delay is
re-activated if the power supply is shortly interrupted.
8
Operation and operational states
Before commissioning the device, please ensure that:
•
the device has been installed in the correct slot and in accordance with the standards
•
the device is not damaged
•
the cables are connected properly
9
Maintenance and repair
It is recommended that all repairs to our devices be carried out by R. STAHL. In
exceptional cases, repair may be performed by approved third-parties.
The devices are maintenance-free.
Troubleshooting chart:
Error detection
"PWR" LED not lit
Output signals faulty
If the procedure described above does not obtain the desired result, please contact your
local R.STAHL sales and service representative. In order to quickly process your request,
please provide us with the following information:
•
•
•
•
10 Accessories and spare parts
Use only original accessories and spare parts from R. STAHL Schaltgeräte GmbH.
Programming set 9199/20-01
20
Frequency Transmitter Type 9146
Malfunction cause(s)
Power supply failure or device
fuse is defective
Sensor is incorrectly connected
Sensor does not work acc. to
NAMUR
Type and serial number,
Purchase date(s),
Description of the error,
Application description (particularly the configuration of the
input/output circuitry)
Consists of PC software for Windows 98, NT, 2000
and XP and a programming cable for PC's
equipped with an RS 232 interface
Version 3.xx or higher is required for the 9146
Trouble-shooting
Check power supply.
If device fuse is defective, send device in for repair.
Check connections (see 6.1)
Potential free contacts acc. chapter 7.2 need additional
resistors in series and parallel.
english