Operating Instructions
5
Engineering
5.1 Max. ambient temperatures
The IS pac isolators can be used over a wide temperature range. Depending on the
isolator version and installation method different maximum ambient temperatures may
result.
Ventilation:
without ventilation
Installation:
Single unit
Orientation:
any
Type:
1
70°C
9146/10-11-12
2
9146/20-11-11
70°C
Ventilation:
with ventilation
Installation:
Single unit
Orientation:
any
Type:
1
9146/10-11-12
70°C
2
9146/20-11-11
70°C
5.2 Power dissipation
Data sheets are describing the maximum power dissipation in standard operation (output
20 mA; power supply 24 V DC; load = 250 Ω). In practice not all isolators are working with
full load. Therefore engineering is done typically with an average power dissipation of 70 %
(P
).
70%
Type
Channels
9146/10-11-12
1
9146/20-11-11
2
14
Frequency Transmitter Type 9146
DIN-rail
vertical
horizontal
50°C
65°C
50°C
65°C
DIN-rail
vertical
horizontal
60°C
70°C
60°C
70°C
max. power dissipation
1,1 W
1,5 W
english
pac-Carrier
vertical
horizontal
40°C
60°C
40°C
60°C
pac-Carrier
vertical
horizontal
50°C
65°C
50°C
65°C
70 % power dissipation
0,77 W
1,05 W