IQ8Wireless transponder for wall mounting
9

Assembly

Loos housing screw  and open housing.
Mark the mounting holes according to Fig. 15.
IQ8Wireless transponder should be installed with suitable fixing material (plugs and
screws) in the proper position on a stable wall surface with no mechanical stress of the
housing.
The mounting place location of the IQ8Wireless transponder should be chosen
so that a good wireless link (field strength) between the transponder and the
assigned IQ8Wireless detector bases is guaranteed. The transmission quality
can be checked with the programming software tools 8000.
Observe that the IQ8Wireless transponder must not be installed on walls with
metal grating or which are filled with aluminium foil-insulated glass wool and
which could thus seriously affect the wireless communication.
172
Top
Fig. 15: Fixing points on the back of the housing (sizes in mm)
A
red green
B
red green
Fig. 16:IQ8Wireless transponder in housing with display LED and aerials (sizes in mm)
30
39
LED 1
LED 2
LED 3
LED 4
1
Top
200
FB 798941.10 / 02.11

Quicklinks ausblenden: