INSTALLATION
POwER SUPPLy
4.
Power supply
A1
Integrated control unit (in the ventilation unit)
A3
Control unit in the wall mounted enclosure
X5
Terminals for external CAN-BUS
X27
6-pole CAN-BUS socket plug for controls
»
Make a link between the ventilation unit and the control unit
with the already routed data cable.
»
Use the 6-pole terminal strip provided as a plug-in connection
to the control unit.
Be sure to get the polarity right on the ventilation unit and the
control unit:
Ventilation unit connections:
X5 - terminal 7
= Gnd
X5 - terminal 8
= CAN-Low
X5 - terminal 9
= CAN-High
X5 - terminal 10 = +Ub
Connection to the control unit:
X27 - terminal 1 = CAN-High
X27 - terminal 2 = CAN-Low
X27 - terminal 3 = Gnd
X27 - terminal 4 = +Ub
X27 - terminals 5 and 6 are unassigned
6 |
4
FES Comfort | TCR Comfort
6
5
A3
4
3
2
1