Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Characteristics; Troubleshooting - Elkron EL20RT/05 Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 21
First powering up
At first powering up, after the columns have been fixed one in front of the other, the beams are automatically synchronized by
the optical signal.
The Coding of TX coupling with RX is performed automatically
The receiver Led indicates any malfunctions:
- Led OFF: relay closed, barriers are functioning correctly
- Quick-flashing Led: see section titled "Troubleshooting"

Technical Characteristics

• RX-TX power supply nominal voltage ........................... 12 V—
• RX-TX power supply min-max ....................................... 10,5 - 15 V—
• Absorptions (typical-max) transmitter with 12 V—
EL20/05T ........................................................................ 11 mA typ - 16 mA max
EL20/10T ........................................................................ 13 mA typ - 20 mA max
EL20/15T ........................................................................ 15 mA typ - 24 mA max
EL20/20T ........................................................................ 17 mA typ - 28 mA max
• Absorptions (typical-max) receiver with 12 V—
EL20/05R ....................................................................... 16 mA typ - 20 mA max
EL20/10R ....................................................................... 22 mA typ - 26 mA max
EL20/15R ....................................................................... 28 mA typ - 32 mA max
EL20/20R ....................................................................... 34 mA typ - 38 mA max
• Max range (adjustable on two levels) ............................ 10 m (Outdoor inst.)
• Alarm times .................................................................... >0.1 sec (one ray interrupted)
• Emitters wave lenght ...................................................... 940nm
• Issued signal .................................................................. PM transmission (pulse mode)
• Operating temperature certified (rules CEI) .................. -25°C - +55°C
• Alarm relay contact ........................................................ 0,1 A@24V— with serial protection R=10 Ohm
• Anti-tampering/anti-removal microswitch ..................... 50 mA@12 V—
• Degree of protection declared by builder ....................... IP65 IK04
• Degree of protection certified (rules CEI) ...................... IP34
• Fault indication ............................................................... Red LED flashing
• Size and weight
EL20/05 .......................................................................... 500 x 25 x 23 mm - weight 250 g
EL20/10 .......................................................................... 1000 x 25 x 23 mm - weight 500 g
EL20/15 .......................................................................... 1500 x 25 x 23 mm - weight 750 g
EL20/20 .......................................................................... 2000 x 25 x 23 mm - weight 1000 g

Troubleshooting

Trouble
Led is lit with fixed light
and the relay contact is
open.
Led is flashing and the
relay contact is open
Led is always OFF and
the relay contact is open.
Led is lit with fixed light
and the relay contact is
closed
Led is always OFF and
the relay contact is closed.
Possible Cause
• Incomplete acquisition of random code
• Power supply to TX column missing
• Barrier is excessively off-center
• Range selection jumper is not set correctly
• RX column fault
• Power supply to RX column missing
• Alarm memory enabled
• TC present
Via Carducci, 3 - 10092 BEINASCO (TO) - ITALY
TEL. +39.011.3986711 - FAX +39.011.3499434
MIN RANGE
AT REST
1 sec (two adjacent rays interrupted)
• Check that there are no obstacles
• Supply TX column
• Re-position barriers
• Check the distance between barriers and
• Check the RX column and replace, if
• Supply RX column
• Arm the system and disarm, if necessary
• Arm the system and check connections
ELKRON S.p.A.
www.elkron.it
e-mail info@elkron.it
8
MAX RANGE
38 mA typ - 47 mA max
64 mA typ - 73 mA max
90 mA typ - 99 mA max
116 mA typ - 127 mA max
WITH ALARM
14 mA typ - 18 mA max
20 mA typ - 24 mA max
26 mA typ - 30 mA max
32 mA typ - 36 mA max
20 m (Indoor inst.)
Corrective Measure
between barriers
select the correct range
necessary
(refer to the TC input)
EL20

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

El20rt/10El20rt/15El20rt/20

Inhaltsverzeichnis