Herunterladen Diese Seite drucken

Refco Gobi II Montageanleitung Seite 3

Vorschau ausblenden Andere Handbücher für Gobi II:

Werbung

4
5
When Indoor Evaporator Unit is powered from the Outdoor Condenser Unit
Evaporator Unit (Indoor)
L
N
**Orange:
To use fail-safe
operation.
1. Remove the violet wire
from indoor live.
NC
NO
COM
2. Connect the orange
wire to indoor live.
3. Change alarm relay to
fail-safe operation.
NO
COM
NC
Condensate Pump
**Orange:
To use fail-safe operation.
1. Remove the violet wire from indoor live.
2. Connect the orange wire to indoor live.
3. Change alarm relay to fail-safe operation.
(typical) Data
3
Earth
Neutral
100-240vac~
Alarm Relay Operation Table
L
N
Power Up LED Sequence
Pump Status
Condensate Level
Alarm
Relay
Unpowered
N/A
Powered
Below Alarm Level
Powered
Alarm-Activated
Condenser Unit (Outdoor)
3
N
N
L
L
Default
Operation
VRF Condenser Unit
(Outdoor)
N
L
To change Alarm Relay Operation:
1. Unplug pump
2. Move DIP switch positions to
3. Plug pump in
4. Wait for one green LED blink
5. Move DIP switch positions to
6. Wait for one red LED blink
7. Reset DIP switch positions to
8. Wait for one green LED blink
9. Unplug pump
10. Set the DIP switches back to the desired capacity
configuration. (Low, Medium-Low, Medium-High, High)
11. Plug Pump in and check that power up LED sequence
matches the desired alarm relay operation
12. Done.
To reset default alarm relay operation repeat
steps 1 thru 11.
When Multi-Split System is installed
Fail-Safe
Evaporator Units (Indoor)
Operation
3
N
(typical) Data
3
Earth
Neutral
N
100-240vac~
L
View installation video at www.condensate-pumps.com
L
Safety Circuit
NC
NO
COM
NO
Alarm
Relay
COM
NC
Blue
N
Brown
L
Condensate Pump

Werbung

loading

Verwandte Produkte für Refco Gobi II