Connection To Mains And Loads - Secomp Roline Prosecure Ii 700 Va Benutzer- Und Installationshandbuch

Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

Connection to mains and loads

The following Input and Output cables come supplied with all models
700 VA, 1000 VA,
1500 VA, 2000 VA
3000 VA
l Ensure that the UPS is disconnected from mains and loads while connecting the External Battery
Cabinets, if needed.
l Use the battery cable that comes with the External Battery Cabinet to connect the External Battery
Cabinet to the UPS. Connect a second battery cabinet to the first one with the cable provided if more
than one is to be installed.
l Be aware of UPS parameters and changing the Battery pack quantity when using the external battery
cabinets (see chapter 7.2)
l Connect the Input cable to the UPS and connect the other end to a grounded outlet. The batteries will
automatically charge when connected to the mains. Please realize that although you may start using the
UPS immediately, maximum back-up time will still not be available, so it is recommended to charge
the batteries for a minimum of 8 hours before use.
l If unit instantly shows a "Site Wiring Fault", rotate the connector (Schuko) (see chapter 7.4).
l After charging, connect the loads to the UPS (see the example in fig 3).
l Do not connect any devices that have the possibility of overloading the UPS or drawing half-wave
rectified current, such as hair dryers or vacuum cleaners.
l Should computer or alarm connections be used, use connections according to chapter 6 of the manual
provided with that option. The connections can be referred to on the rear panel.
l The installation is now complete
(option)- IEC 320 10 A (Input cable)
Two IEC-IEC 320 10 A (Load cable)
(option)-IEC 320 16 A (Input cable)
Two IEC-IEC 320 10 A (Load cable)