1. Open the lid more than 180° by hand.
A
2. Pull the lid upwards and out from the casing and unhinge the lid.
Closing the lid
After the transmitter has been mounted in place and the cables have
been installed with the cable glands, the lid can be closed.
1. Close the lid.
2. Press the lid gently downwards by hand.
3. Check that the lid snaps into its closure position.
4. Mount the lid securing screw using a PZ1 (Pozi) screwdriver.
Note! The lid securing screw is not mounted at delivery
but packed separately.
Caution! The securing screw should be mounted all the
way to the bottom but only tightened loosely. This is to
prevent the screw from damaging the plastic, which could
render the screw ineffective.
Wiring
1
4
2
GND A- B+
G0
Number
Description
1
Display
2
Joystick with Menu button
3
Supply voltage terminal
4
RS485 terminal
Settings
The joystick is used to manoeuvre through the channels (see Table 1).
For each selected channel four different values are shown subsequently
in the display:
1. Current channel, e.g. 01
2. Received signal strength indicator (RSSI), S.1...9
S. = signal strength, 1 = weak signal, 9 = strong signal
If S.1 to S.2 is shown, the signal is too weak to have a good
connection. Place the sensor in a different place or in a different
orientation.
S.- = no sensor is paired on the selected channel
Note that the signal strength abbreviation S. should not be mistaken
for number 5.
3. Value 1 for the sensor or detector (if available), 0...99. If both value
1 and 2 are available, value 1 always shows the temperature.
4. Value 2 for the sensor or detector (if available), 0...99. Value 2 can
for example show the humidity.
Note! A minimum of -90 dB is recommended for the in-
coming signal for full wireless functionality. The signal
strength can be seen in Modbus.
RCW-M32
Table 1 Navigate the channels
Description
Activate the display
Move to the subsequent channel.
Move to the preceding channel.
3
Jump 8 channels forward.
Leave the menu and inactivate the display.
G
Many default settings can be changed via the display. The joystick is used
to navigate within the menu as shown in Table 2. To enter the menu,
press the Menu button for 4 s when the display is inactive. Six levels are
available:
1. A: Pair and unpair sensors
2. B: Modbus addresses, as hexadecimal numbers
3. C: Communication speed (baud rate)
4. D: Parity and stop bit
5. E: Selected frequency
6. F: Current software version
Table 2 Navigating the menu
Description
Enter into the menu
Move between the different levels in
the menu (A-F)
Enter into one level
Move between different values within
one level
Leave the menu and inactivate the
display.
A complete description on how to read and modify the settings, both via
the display and via Modbus, can be found in the RCW-M32 variable list
on Regin's website www.regincontrols.com
Note! After a power cut of the receiver, the sensor and de-
tector readings will be set to temporary values. The re-
ceiver awaits new readings from the sensors before
communicating with the controller again.
Manoeuvre
Time
Press the Menu
1 s
button
Push UP
1 s
Push DOWN
1 s
Push RIGHT
1 s
Push LEFT
3 s
Manoeuvre
Time
Press the Menu button when
4 s
the display is inactive
Push UP or DOWN
1 s
Press the Menu button
1 s
Push UP or DOWN
1 s
Push LEFT
3 s