Switch-off times:
Eaton Industries (Austria) GmbH, Eugenia 1, A-3943 Schrems
www.eaton.eu/documentation
Electrical:
Operating voltage Ub
Rated current IN
Current switch-off
(in case of overload or short circuit)
Switch-off times for
electronic switch-off
Capacitive loads
Inductive loads
Mechanical:
Number of channels
Width
Height
Depth
Input terminals (optional)
Output terminals
Terminal type
Terminal capacity
Busbar
Assembly
Status LED
Slide switch
Text field
Degree of protection
Ambient temperature
Storage temperature
Rated
Switch-off time
Current
(typically)
I
N
2A
460ms
4A
240ms
6A
160ms
8A
108ms
10A
108ms
13A
75ms
16A
75ms
24 DC (16....30 V DC)
Fix; 2, 4, 6, 8, 10A
Typically 1.3 x I
with active current limitation to
N
1.2 x l
N
see time / current table
Up to 20,000μF
I
≤ 6A ... τ
≤ 60ms
n
max
6A < I
≤ 10A ... τ
n
max
10A < I
≤ 16A ... τ
n
max
1
17.5 (1 HP)
92.5mm
119.2mm
3 x LINE (+) and 3 x GND (-)
3 x LOAD (+) and 3 x GND (-)
Push-in terminals
2.5mm² (flexible with ferrule)
4mm² (rigid)
LINE (+) and GND (-); max. 80A
In different lengths up to 1m
Snap-fit onto the TH35 mounting rail (EN 60715)
Two-colored; Green = OK; Red = Tripped
Off = channel not in operation
On/Off/Reset
17.5 x 6mm
IP 20
-30°C to 55°C
-40°C to 100°C
active current
limitation
1.2 x I
N
1.2 x I
N
1.2 x I
N
1.2 x I
N
1.2 x I
N
1.2 x I
N
1.2 x I
N
5
≤ 12ms
≤ 7,5ms
MA-PXS24_Economy.docx/02.2018
150501508/IL019189ZU