door temperature.
•
The water circuit is properly connected (no leaks or damage to the hydraulic connections, the con-
nections are properly tightened).
•
The electric circuit is properly connected (the cables are tightly secured to the terminals and inter-
mediate circuit-breaker), properly insulated, and connected to the earthing connection.
•
The conditions of installation and use described above have all been met.
•
The outdoor temperature is between -3 and +43°C.
•
The water temperature is of 15°C minimum.
•
The evaporator at the rear/on the sides of the HP is clean (leaves, dust, pollen, cobwebs...)
You can now start your device by following, in the given order, the following steps:
•
Open the 3 valves of the bypass (refer to the hydraulic diagram).
•
Half-close the bypass valve.
•
Remove all unused items or tools from the area surrounding the HP.
•
Start the pump of the filtration system.
•
Power up the HP by engaging the circuit-breaker and using the ON/OFF button of the display.
•
Check that the HP starts and stops in sync with the filtration circuit: if no water is detected in the HP,
the display shows "FLO"
•
The HP starts after a delay of a few minutes.
•
Adjust the temperature ("Regulation" chapter).
•
Adjust the water flow ("Water flow setting" chapter).
•
After a few minutes, you can adjust the bypass valve as indicated in the "Water flow setting" chap-
ter. Having completed the above steps, cover the pool and let the HP operate for a few days with
the filtration pump in "forced mode" until the water of the pool reaches the desired bathing tem-
perature.
SETTINGS
Water flow setting:
•
To optimize the heating performance and achieve power savings, the flow of water travelling
through the HP should be adjusted.
•
The adjustment is done based on the reading of the water flow indicator present on the heat pump
display :.
Very low water flow
Low watre flow
Optimal water flow
High water flow
•
The adjustment is done by opening or closing the adjustment valve of the bypass.
•
To reduce the water flow: reduce the amount of water passing through the HP: open the bypass
adjustment valve.
•
To in crease the water flow: increase the amount of water passing through the HP: close the bypass
adjustment valve.
•
During normal operations, the inlet and outlet valves must remain fully open.
Normal pressure:
- 27 -