The HA59 is a heat detector meant to discover cases of fire in the first phase. If the temperature rises, the HA59 will
EN
start emitting a loud alarm tone of at least 85dB (A). It's advisable to test the heat detector weekly by using the test
button. Attention: This heat detector only signals when the temperature rises to 54˚C or higher. It doesn't directly
detect smoke or fire. Save this manual in a secure location, like the fuse box cabinet.
RECOMMENDED INSTALLATION LOCATIONS FOR THE HA59:
Install the heat detector in areas where you cannot place a smoke detector. Ensure that it is placed in a location that
ensures that, if there would be a fire nearby the detector, the escape route is still accessible.
Use multiple detectors to increase your safety and to ensure an escape route will be available in case of fire.
It's advisable to place one heat detector in every location where there is no smoke detector.
Place at least one heat detector in the kitchen and garage, where equipment present may cause fire.
Both heat and smoke will first move upwards, to the ceiling. Then it will travel horizontally. Wall-mounting may technically
be possible but will result in slower alarm.
When mounting the detector to the ceiling, place it at a minimum distance of 50 cm from any wall and 61 cm from any
corner. Due to natural air flow, such corners will slow or prevent detection of heat.
AVOID THE FOLLOWING LOCATION INSTALLATIONS:
Keep away at least 3 meters from any cooking apparatus.
Do not place in the bathroom; hot showers may cause false alarm.
Do not place near a fan or near the exhaust of an airconditioner or heater.
Do not place in the nook of an A-shaped ceiling.
Do not place in rooms where the temperature can reach below 4°C or beyond 38°C.
Do not paint the heat detector and do not cover it in any way.
INSTALLATION INFORMATION:
Place the ceiling plate in a suitable location using the 2 plugs and 2 screws on the ceiling or wall.
Then screw the heat detector onto the ceiling plate. Note! You will immediately hear a loud beep once, confirming that
the heat detector is working. The detector is now ready for use. Every 30 seconds, the red LED will light up briefly to
indicate that the heat detector is in operation.
USE, TESTING AND MAINTENANCE:
Operation:
The heat detector is operational as soon as the heat
detector is screwed onto the ceiling plate is turned.
When the detector is operating the red LED lights up
briefly every 30 seconds. The moment the detector rises
above 54°C in the heat, the alarm will triggered by an
alarm tone and the red LED flashes rapidly.
When the heat disappears, the alarm automatically stops.
Testing:
By pressing the test button on the HA59, the alarm can be tested. Operation is correct if the red LED lights up briefly and
a signal tone is heard. Check the detector preferably every week. In alarm status, the heat detector generates at least
85dB(A) sound pressure. Do not test the heat detector with candles, open flames, cigarettes and the like. If necessary,
you can test the heat detector with a hair dryer.
9V BLOCK
Niet in deze ruimte
In de buurt
Not in this space
van deze ruimte
Near this space
90 cm
90 cm
minimaal
minimaal
90 cm
90 cm
minimum
minimum
50cm / 20" minimum
60 cm minimaal
dead air
dode
luchtruimte
space
Ceiling plate
HA59 Heat
detector
Test button

Werbung

loading

Verwandte Produkte für Alecto HA59