GC 403
WDS
Scope of delivery
4.2
Wind-
and
rain
sensor
GC 402 W VS (Mat. No. 140229)
Consists
of:
Wind speed sensor GC 402
wvs
2
Clamp ring
Rain sensor (24 V DC/AC)
3
with equipment bracket
GC 401
RS
Bracket (aluminium) for
4
pole or wall mounting
Functioning of a wind direction-dependent control (according to DIN 18232-2)
4.3
With no wind and wind speeds < 1 m/s, all NRA/RWA and air supply areas in the outer walls of the smoke section
are opened. At speeds > I m/s, only the supply air and NRA/RWAareas in the respective downwind wall surfaces
are opened. The wind speeds and wind directions are measured above the roof and averaged over a period of 10
± 2 minutes.
Operating requirements MBZ 300:
4.4
In addition to the wind direction transmitter, connection and configuration requires wind sensor and, if necessary,
rain sensor:
Weather
module
Licensed software for configuring the MBZ 300
Seethe central description for connection, and description of the software MBZ 300 for setting.
Assembly
5
To mount the wind speed and rain sensor, see Installation
402 WVS" (Mat. No. 143015)
For the connection to the RWAcentre MBZ 300, see description of the centre; configuration of the wind direction-
dependent control for the MBZ 300 requires a licensed software of the manufacturer of the centre.
Installation
of the wind
5.1
The switching point for the wind speed sensor for the ventilation operation must be adapted to local conditions.
The smallest wind speed is set at the factory.
o The sensors are mounted on the side of the building that faces the weather. Surrounding buildings and
electrical equipment must not impair their function.
The console
must ensure a secure hold even in extreme
a Mount wind direction transmitter
The mounting position must be chosen in such a way that wind direction and wind speed can be ideally
determined (e.g. above the roof).
The north-marking of the wind direction transmitter must face exactly north.
set GC 401
RS /
2
3
4
WM
direction
transmitter
and wind speed sensor on one pole for perfect measurement
Wind
direction
GC 403 WDS (Mat. No. 140228)
Consists
5
5
6
7
6
7
8
8
Instructions
„Wind and Rain Sensor Set GC 401 RS/ GC
weather
conditions
(storm).
Assembly
transmitter
of:
Wind
direction
transmit
ter GC 403 WDS
C amp ring
Bracket for pole or wall
mounting
Connection
box
110x
110 x 66 mm
to
connect
to MBZ 300.
Cable:6 x 0,34 mm2
LIYY,3m ong (w/o Fig.)