to allow water being drained or pumped to be fully vacated
or just to prevent nuisance switching.
SAFETY FIRST
Disconnect all power supplies before starting installation
or maintenance work. The interconnecting conductors and
connections are to be confined within the host equipment.
All wiring and connections are for internal installation only.
This product must be installed only by competent engi-
neers. There are no user serviceable parts in this control.
Do not use if damaged in any way. Check the label to ensu-
re this product is the correct voltage.
INSTALLATION
The AquaSwitch is intended to detect rising condensate
water levels in A/C and Refrigeration applications. It may
also be used in Reservoir Top-Up or High Level Alarm ap-
plications. The AquaSwitch is a semi-submersible switch
therefore it must not be used in application where it will
be permanently submerged or for long extended periods.
It is not recommended to use it as a low level switch. The
AquaSwitch may be used in metal or plastic collection trays.
When positioning, ensure that there is 8 mm of clearance
in front and 5 mm below the sensing pads. The AquaSwitch
will operate tilted in any direction from the normal by up to
45° however for reliable operation position the AquaSwitch
flat and level. Tray depth must be at least 17 mm to prevent
overflowing.