SETUP settings menu:
After opening SETUP, submenu 100 appears. → Open menu 100.
↑, ↓ Menu 200 - 600 & 800, with optional Modbus: 200 - 800
(locked with password → Reference Manual)
Un
Rated voltage (correct setting is very important)
For voltage monitoring and stages database reference.
Ct
Current transformer ratio (must be set)
The value is used for calculation and activation of some
measurement values in the measurement menu.
Pt
Voltage transformer ratio
Important as the basis for setting Un
AI
Automatic initialisation
→ section Incorrect connection/ AI – Automatic initialisation
PFC
CONTROL ON/ OFF/ HOLD
Switching on, switching off, freezing the control
CP1
Target cosϕ 1
Basis for compensation target
St
Switching time
Defines the speed of the controller
OUt
Stage type
Defining stage type: AUTO, Fon, Foff,
Reset faulty stages (FLty)