Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - S+S Regeltechnik Kinasgard Rbwf -Up Bedienungs- Und Montageanleitung

Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

G
®
KINASGARD
RBWF - UP
The motion sensor KINASGARD
and motions and has a switching output (normally open). The room motion sensor
is used for the observation and recognition of conditions and for the motion-
dependent control of room functions, e.g. for lowering temperatures in unused
rooms. This motion sensor is used for in-wall installation in corridors, in offices,
in residential rooms and business facilities in connection with light switch
programmes. The sensor detects motions over an aperture angle of 110° and
a perimeter of 360°. Because of the patented lens system with 20 individual
lenses, only very small dark areas are resulting, which even at a distance of 10 m
are only a few centimeters wide, safely detecting also small motions.

TECHNICAL DATA:

Power supply: ........................ 24 V AC ⁄ DC
Power consumption: ................ < 1 VA at 24 V DC
Sensor:................................. infrared motion sensor
Detection range: ..................... perimeter 360°,
Motion detection: ................... of persons and objects,
Output: ................................. without ⁄ with motion,
After-running time: ................. adjustable from 4 s to 16 min
Ambient temperature: ............. 0 ...+ 50 °C
Enclosure: ............................. plastic
Mounting: .............................. in in-wall flush box Ø 55 mm, in-wall
Electrical connection: .............. 0.14 - 2.5 mm²,
Protection class: .................... III (according to EN 60 730)
Protection type: ..................... IP 20 (according to EN 60 529)
Standards: ............................ CE conformity, electromagnetic compatibility
SWITCH PROGRAMME:
Manufacturer: .......................... Busch-Jaeger Reflex Si
Enclosure: ............................. plastic,
Type ⁄ WG1
RBWF - UP
R B W F - U P - S
®
RBWF-UP detects the presence of persons
aperture angle 90° ⁄ 110°,
reach ca. 10 m, circular
necessary temperature difference
between subject and ambience ≥ 5 K
potential-free changeover contact 24 V
via plug terminals on circuit board
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC
(other switch programmes, manufacturers,
colours and prices upon request)
standard colour alpine white (similar RAL 9010)
(other colours are possible on request
with colour variants depending on the respective
light switch programme)
Detection
Presence ⁄ Motion
Yes ⁄ No
Schematic diagram
Output
Presence ⁄ Motion
Normally open contact
5
5
6
6
Normally open
contact 1
contact 2
(closing when motion
is detected)
GND
UB -
GND
UB +
2
2
1
1
Item No.
1401-51 10-1000 -000
RBWF - UP
3
3
4
4
Inhaltsverzeichnis