Herunterladen Diese Seite drucken

Pixsys TD Serie Installationsanleitung Seite 7

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Cut-out
Lc + 2 mm
Hc + 2 mm
Dimensions
Hc
Models
TD710
TD810
TD815
TD820
TD830
* Dimensions refer only to the product without the size of terminals and cables.
5
Power supply and grounding
Danger!
This device is only permitted to by supplied by a SELV / PELV (class 2) power supply or with
safety extra-low voltage (SELV) in accordance with EN 60950.
Caution!
24VDC power supply line must be protected by a 1,0A fuse.
Caution!
Functional ground must be kept as short as possible and connected to the largest possible
wire cross section at the central grounding point (e.g. the control cabinet or system).
Fig. 1
Suggested
thickness/
Spessore
suggerito
0÷8 mm
Wc
W
L
H
204
160
274
216
268
191
317
256
406
270
Connect a 24VDC 1,0A (min.) power supply, as showed into the
figure. Connect the device grounding with a conductor of 18AWG
(2,5mmq) minimum section. For the whole series it is suggested to
use a 24 VDC 1,0A 24VA power supply (Pixsys code 2700.10.008).
Use Copper, Copper-Clad Aluminium or Aluminium conductors wire
for all electric connection.
Fig. 2
Lc
D
L
W *
Wc *
41
35
40
31
43
35
42
33
50
41
H
Lc
Hc
181
144
260
200
255
177
302
242
391
255
User manual - HMI Series - 7
USB 1

Werbung

loading

Verwandte Produkte für Pixsys TD Serie

Diese Anleitung auch für:

Td 710Td 810Td 815Td 820Td 830