10. Technical Data.
Operating Range - 5 to 50 metre system
•
Operating Range - 50 to 100 metre system 50 to 100 metres
•
Supply Voltage
•
Quiescent Current (no lamp illuminated)
•
Alarm Current
•
Fault Current
•
Power Down Reset Time
•
Operating Temperature
•
Tolerance to Beam Misalignment at 35%
•
Fire Alarm Thresholds
•
Optical Wavelength
•
Head Maximum Size
•
Weight
•
11. Service / Application Notes.
For full compliance with BS5839 part 5, use 25% and 35%(default) thresholds. The threshold of 50% is
•
recommended for hostile and extreme environments.
Red LED indicates FIRE.
•
Amber LED flashing once every 2 seconds indicates FAULT.
•
Amber LED flashing twice every 2 seconds indicates AGC FAULT.
•
12. Parts List.
1 off: Detector Head Assembly
•
1 off: Prism for the 5 to 50 metre system
•
4 off: Prisms for the 50 to 100 metre system
•
1 off: Dual Test Filter
•
0044-023-01 14.11.08
5 to 50 metres
10.2Vdc to 30Vdc
<4mA
Dependant on Zone Power (470 Ohms)
<4mA
<2 seconds
-30°C to 55°C
Detector ± 0.8°, Prism ± 5.0°
2.50dB (25%), 3.74dB (35%), 6.02dB (50%)
880nm
Width 130mm, Height 210mm, Depth 120mm
740 gm
10