Previous month's values "LOOP 2"
Previous month's values
Log date
Amount of energy at the
reporting date
Cooling registers at the
reporting date (optional)
Volume at the reporting
date
Missing time on set day
Max. flow on set day in 2
s cycles with date stamp
General/Communication "LOOP 3"
General/Communication
Device number,
7-digit
Optional interface
Primary address (only
for M-Bus)
Secondary address
7-digit - for M-Bus
Other "LOOP 4"
Other
Date
Time
4.1
Monthly values
The meter stores the following values for 24 months on the
monthly set day
Missing time
Volume
Energy
and the maxima with date stamp for
Flow
Power
Temperature hot side
Temperature cold side
4.2
Parameterization
When the LCD displays the code input, you can access the
parameterization operation by entering the code. You can set
date and M-Bus primary address in the parameterization oper-
ation for example. For more detail see the separate parameter-
ization instruction.
5.
Getting started
For activation proceed as follows:
Open the slide valves slowly.
Check the heating system for leak-tightness and bleed air
out carefully.
Press the button on the meter briefly.
The message "F0" disappears after 10 sec.
Check the measured values for flow and temperatures for
plausibility.
Vent the heating system until the flow display is stable.
Meibes System-Technik GmbH
Max. power in 2 s
cycles with date
Error messages for incorrect installation:
stamp
Max. temperature hot
side in 2 s cycles with
date stamp
Max. temperature cold
side in 2 s cycles with
date stamp
6.
Yearly set day
If the respective operation thresholds are exceeded and flow
and temperature difference are positive, the meter summates
Monthly set day
the energy and the volume.
Firmware version
For a positive flow the activity display
CRC-Code
loop in the LCD.
All segments of the display are switched on for control purpos-
es during the segment test. The flow, power and temperature
difference are recorded with the appropriate +/- signs.
The operating hours are counted from the first connection of
the power supply. The meter saves "operating time with flow"
Code entry for test /
as soon as a positive flow is recognized. Missing hours are
para operation
summated if there is a fault, and the meter is thus unable to
take a measurement.
Stored maximum values are marked with an „
right-hand area of the LCD.
Subject to change without prior notice
Fit the user locks to the fittings and the temperature sen-
sors. The scope of supply includes two self lock seals for
sealing a sensor and the connecting fitting.
Read the meter status for energy, volume, operation and
missing time and note the values.
Error "incorrect flow direction (negative)"
Check that the flow direction arrows on the volume measurement unit
match the flow direction of the system. If the directions do not match,
turn the volume measurement unit by 180°.
Error "negative temperature difference"
Check whether the sensors are installed in the right circular flow (flow
and return flow interchanged). Use only a meter suitable to the mount-
ing place.
Heat meter:
Temperature sensor in the flow-pipe with higher temperatures; temper-
ature sensor in return-pipe with lower temperature
Cooling meter:
Temperature sensor in the flow-pipe with lower temperatures; tempera-
ture sensor in return-pipe with higher temperature
Functional details
If the operate margin is gone below a "u" is displayed at a leading
point for the flow, power and temperature display.
appears in the user
" in the lower
01.07.2022
12