K-factor conversion table (Flow only)
The k-factor given by the equipment (k₁) is entered into the equation and the result (k₂) is entered into the PTH.
Example of calculation:
The k-factor data for the equipment is declared to be 5.6 based on liter per seconds [l/s]. You want the PTH to handle flow in cubicmeters per hours [m³/h].
On the second row you will find the equations for k₁ in [l/s].
In the first column you will find equations for k₂ in [m³/h].
k₂ = k₁ * 3.6
k₂ = 5.6 * 3.6
k₂ = 20.16
Enter 20.16 into menu point Set4 [
The VCH display will now show the calculated air flow in cubicmeters per hours. Remember to place the m
m
3.6
0.001
3600
3600
1.699
k-Factor conversion table
]. Please remember to set the dot position before setting the value.
k
= k
* value (k-factor to enter into PTH-3202-DR)
2
1
3
/h
l/s
0.278
1000
1000
0.472
3
m
/h x 1000
l/s x 1000
1000
0.0036
0.001
0.278
1699
© 2021 OJ Electronics A/S
/h sticker on the PTH front.
3
3
m
/s
0.001
0.278
1000
471.9
cfm
0.589
2.119
588.6
2119
2119
BR1032A010a