Function and features
• Flush installation of ifm TA / TT temperature sensors with 10 mm
diameter.
• The clamp fitting is adaptable for various process fittings
(Aseptoflex adapters to be ordered separately as accessories.
• The installation depth of the temperature probe can be adjusted to
suit the particular application.
Permissible overl. pressure: 50 bar.
The inner contact faces of the thread are greased with a food-grade
greasing paste (USDA-H1 84-201)
A
B
C
D
E
F
All manuals and user guides at all-guides.com
A = temperature sensor
B = locking nut
C = spacer ring
D = clamping ring
E = O-ring (Viton)
(You can replace it by the
supplied EPDM O-ring).
F = clamping device
Installation
1
1. Slip the thread onto the temperature probe and set the probe to the
requested installation depth (L).
2. Tighten the locking nut (B) and the clamping device (F) with a span-
ner / torque wrench.
Tightening torque: 25 Nm.
The tightening torque is important to guarantee the pressure
resistance of the clamp connection up to 50 bar.
For mounting the Aseptoflex adapter see installation instructions of
the adapter.
When removing the sensor, the clamping device (F) should be
blocked by means of a spanner to avoid loosening of the clamp-
ing device.