Functions
x
4
8
+
1
IQ
min
Lighting control stay-'ON' time
The lighting stay-'ON' time can either be
set to a fi xed period of between 1 and
30 minutes or is automatically matched in
"IQ mode" to the time persons spend in
the detection zone.
x
5
x min
8
+
Delay
min
HVAC switch-'ON' delay
The switch-'ON' delay for controlling
HVAC can either be set to a fi xed period
of between 1 and 30 minutes or is auto-
matically matched in the "Room surveil-
lance" mode to the time persons spend in
the detection zone.
- Fixed time:
Briefl y press "x min Delay", enter the
chosen time on the number pad; press
"OK" to confi rm.
- Room surveillance:
Briefl y press "
" button.
x
6
Set
8
+
min
Lux
0-50%
Basic illumination 'ON' period
The basic illumination 'ON' period can be
set to a duration in the range of 1 to 30
minutes.
- Briefl y press "x min" button, enter the
chosen time on the number pad, pressing
"OK" to confi rm.
'ON' period for selected brightness
setting
The basic light-level threshold can be
adjusted within a range of 10 to 300 lux.
- Briefl y press "Set Lux", enter the
chosen value on the number pad,
pressing "OK" to confi rm.
PK Elektronik Vertriebs GmbH, E-Mail: info@pkelektronik.com, Internet: www.pkelektronik.com
0
Ok
- Fixed time: Briefl y press "x min" button,
enter the chosen time on the number
pad and press "OK" to confi rm.
- In the IQ mode the stay-'ON' time auto-
matically and dynamically adjusts to
user behaviour. Briefl y press "IQ" button.
1
0
Ok
HVAC stay-'ON' time
The HVAC stay-'ON' time can be set
to a fi xed period of between 1 and
120 minutes.
- Briefl y press "x min" button, enter
the chosen time on the number pad,
pressing "OK" to confi rm.
1
0
Ok
Teach-in
Pressing the "
" button enters current
light level as the threshold for basic
brightness.
Note: To do this, the "Basic illumination
'ON'" parameter must be set to
"in relation to light level" (see 11.9.
p. 18 Calibration description).
www.knx.steinel.de
10
Functions
7
8
+
Test
1
0
Ok
Presence test mode:
"Presence test mode" is used for check-
ing the detection zone. Any movement
detected results in brief fl ashing of the
blue LED. Communication objects are not
sent during the presence test mode.
Lighting test mode
"Lighting test mode" is used for checking
light-level control. To do this, the detector
must have been parameterised by ETS
and its objects linked with the objects of
the buttons and actuators for lighting
control. In this test mode, any movement
detected results in brief fl ashing of the
blue LED. For the duration of this test
mode and irrespective of the parameters
selected for the presence detectors, light-
level control and remote control are acti-
vated for both types of IR remote control,
with lighting control stay-'ON' time being
set to 5 s. The "presence detection" and
"HVAC control" functions are deactivated.
The associated objects are not sent. The
presence detector is re-started after ter-
- Activate presence test mode:
Briefl y press "Test", then briefl y press
"1" followed by "OK".
- Terminate presence test mode:
Briefl y press "Test", then briefl y press
"1" followed by "OK".
minating the lighting test mode. Any
parameters changed at the beginning of
the test mode are now reset to the values
selected with ETS.
- Activate "lighting test mode":
Briefl y press "Test", then briefl y press
"2" followed by "OK".
- Terminate "lighting test mode":
Briefl y press "Test", then briefl y press
"2" followed by "OK".
11