- The luminaire shall be installed by qualified electrician and wired in accordance with the latest IEE electrical regulations
or the national requirements.
- The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced
- During the installation or maintaining the luminaire please use gloves to avoid spots on the cover.
To remove dirt and spots use the following:
- Dust: use micro fiber cloths only.
- Fingerprints, etc.: use cleaner for synthetic materials with antistatic properties.
- Luminaires not suitable for covering with thermally insulating material.
- For controllable luminaires, the classification of the insulation between LV supply and control conductors shall be basic insulation at least.
- Luminaires must not be used or stored in corrosive environment where hazardous materials such as
Sulphur,Chlorine, Phthalates, etc., are present.
I mains (A)
I max
max / 2
Tref
PSU
Imax(A)
16
Tref (us)
200
MCB
I nom.
B-10 A
13
Time (us)
B-16 A
21
C-10 A
18
C-16 A
30
PSD
WIA
PSED/SIA
Electrical characteristics
18,7
4,8
20,4
288
56
195
No. Of luminaires max.
7
32
16
12
50
24
12
52
25
19
85
41
11/18
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
DEVICES