INSTALLATION INSTRUCTIONS
DEHNguard ® M DG M TNC 440 (FM)
Cruciform drive
(e.g.Pozidriv ® Z2)
IEC 61643-1/-11
Class II
Type 2
EN 61643-11: ...
4 Nm
3
1
2
TN-C
DG M TNC 440 (FM)
F1
L1
L1'
L2
L2'
L3
L3'
F2
PEN
A
Fault indication / Defektanzeige
green
test
green
red
press
1
2
1
press
Backup fuse / Vorsicherung
DEHNguard ® M DG M TNC 440 (FM)
F1 ≤ 125 A gL / gG
F1
F2
F1 > 125 A gL / gG
F2
F2 ≤ 125 A gL / gG
A
min. 6 mm² Cu
Protection Module
DG MOD 440
11
14
12
ok
Remote signalling
contact
11
14
12
ok
replace
11
14
12
Protection Module
DG MOD 440
Technical data / Technische Daten
Typ
DG M TNC 440 (FM)
Protection Module
DG MOD 440
U
440 V~
C
max.
125 A gL/gG
ϑ° C
-40°C ... + 80°C
IP Code
20
Coordination / Koordination
LPZ 0
LPZ 1
A
DEHNguard ® M
DG M TNC 440 (FM)
Class I
Class II
Type 1
Type 2
Remote signalling contact / Fernmeldekontakt
DEHNguard ® M DG M TNC 440 FM
U
/ I
N
N
AC:
11
14
12
DC:
max. 1,5 mm²
© COPYRIGHT 2012 DEHN + SÖHNE / protected by ISO 16016
Publication No. 1671 UPDATE 11.12 Id. No. 065988
12 mm
min.
L, N,PE(N),
1.5 mm²
max.
L, N,PE(N),
25 mm²
16 mm² Cu
!
DIN VDE 0185-305-4:...
IEC 62305-4: ...
LPZ 2
LPZ 3
Class III
Type 3
250 V / 0,5 A
250 V / 0,1 A
125 V / 0,2 A
75 V / 0,5 A
12 mm
12 mm
35 mm
≥ 15.5 mm
p.t.o.