The PROmesh P20 is delivered with the following factory settings:
IP Adress
Subnet mask
Gateway
Username
Password
You can customize them with the Service Tool already installed. Connect your PC to one
of the 20 available ports of the switch. Then perform a device scan with the Service
Tool. Make sure that the field „PROFINET device" is selected under the scan settings.
After you have performed the scan, you can adjust the IP address, the subnet mask, the
default gateway and the PROFINET name of the PROmesh P20 according to your needs.
! NOTE
Make sure that the IP address you selected has not yet been assigned. If required, you
can display IP addresses that have already been assigned using the PROscan® Active V2
license software from Indu-Sol.
! WARNING
We recommend to change the factory-set password at the 1st login. It is your responsi-
bility to document this password and protect it against unauthorized access
Accessing the Web User
Interface
The device-specific functions of the PROmesh P20 can be configured via an integrated
webinterface. Open your browser, enter the IP address of the PROmesh P20 configured
in the ServiceTool in your browser bar. Alternatively, you can right-click on the corre-
sponding list entry in the context menu of the ServiceTool to select „to website". The
Web UI now opens in your standard browser.
! NOTE
Further information on the configuration options and troubleshooting can be found in
the supplied manual on our website:
https://sdx.indu-sol.com/s/fZDLQTyzLPg9RPR
14
0.0.0.0
0.0.0.0
0.0.0.0
admin
admin
ENGLISH
Interpreting LED Displays
LED label
Mode
Meaning
VDC1
Green
Voltage at terminal sufficient
Off
Voltage at terminal insufficient
VDC2
Green
Voltage at terminal sufficient
Off
Voltage at terminal insufficient
Status
Green
PROFINET connection to the controller
active
Yellow
PROFINET connection to the controller
inactive
Error
Red
Power failure, port error or configured
alarm active
Off
No malfunction at the port
Data
Green
Connection established
Blinking Sending / receiving data
Off
No connection established
ENGLISH