2.3

Motor terminal (Han 10E)

Notes
Danger
Ensure that the wiring is carried out carefully and correctly. The temperature
sensor terminals must not be connected to 400 V AC. Otherwise motor star-
ters may be destroyed. There is potentially lethal danger!
For this reason, the motor line must be laid in such way that the cable cannot
get jammed or squashed!
Caution
Safe separation between 400 V AC and 24 V DC is only guaranteed on a motor
with safe separation of the temperature sensor circuit with respect to the stator
winding.
2.3.1

Pin assignment

Earthing screw
Pin
1
2
3
4
5
6
7
8
9
10
Fig. 2-4: Pin assignment for motor terminal
ECOFAST Motor Starters
GWA 4NEB 950 5221-12 DS 02
Motor starter
Han 10E socket
10
9
8
7
6
5
4
3
2
1
Motor
Assignment
Winding terminal U1
Winding terminal V1
Winding terminal W1
Brake (reference potential)
Brake
Winding terminal W2
Winding terminal U2
Winding terminal V2
Temperature sensor (terminal a)
Temperature sensor (terminal b)
Earthing screw: PE