Installation in Conformance with EMC
Regulations
Siemens AG
6SE7087-6KP60
SIMOVERT MASTERDRIVES
The following contains a summary of general information and
guidelines which will make it easier for you to comply with EMC and CE
regulations.
♦ Ensure that there is a conductive connection between the housing of
the converters or inverters and the mounting surface. The use of
mounting surfaces with good conducting properties (e.g. galvanized
steel plate) is recommended. If the mounting surface is insulated
(e.g. by paint), use contact washers or serrated washers.
♦ All of the metal cabinet parts must be connected through the largest
possible surface area and must provide good conductivity.
If necessary, use contact washers or serrated washers.
♦ Connect the cabinet doors to the cabinet frame using grounding
strips which must be kept as short as possible.
♦ You must use shielded cables to make the connection between the
inverter and the motor.
♦ The shield of the motor supply cable must be connected to the
shield connection of the inverter and to the motor mounting panel
through the largest possible surface area. If the motor terminal box
is made of plastic, you must use additional earthing litz wires.
♦ The motor cable shield must not be interrupted by output reactors,
fuses or contactors.
♦ All signal cables must be shielded. Separate the signal cables
according to signal groups.
Do not route cables with digital signals unshielded next to cables
with analog signals. If you use a common signal cable for both, the
individual signals must be shielded from each other.
♦ Power cables must be routed separately away from signal cables (at
least 20 cm apart). Provide partitions between signal cables and
power cables. The partitions must be grounded.
♦ Connect the reserve cables/conductors to ground at both ends to
achieve an additional shielding effect.
♦ Lay the cables close to grounded plates as this will reduce the
injection of undesired signals.
♦ Eliminate any unnecessary cable lengths because these will
produce additional coupling capacitances and inductances.