9.3 "APP" CONFIGURATION

In the "APP" CONFIGURATION menu the work mode can be selected. CPC Mode, CFC Mode or Min./Max. Mode Once
the work mode has been selected, the characteristics shown in the following diagram can be configured.
Unit of measure
selection:
CPC Mode: Pa,
kPa, mbar, inWC or
mmWc
SETPOINT selection
RANGE 0 to 2500
SETPOINT selection:
This functions if the
day/night input is
operative
RANGE: 0 to 2500
Proportional band
selection
RANGE: 0 to 20
SAVE CONFIG?
YES
YES or NO
Integral time
selection
RANGE: 0 to 10
Regulator response time selection
RANGE: 0 to 20
WORK MODE
CPC
UNITS OF
MEASURE
PA
PRESSURE REF 1
100 Pa
PRESSURE REF 2
100 Pa
P VALUE
180
VALUE I
4.00
RESPONSE TIME
2 s
CONFIGURATION
APP
WORK MODE
CFC
Unit of measure
UNITS OF
selection:
MEASURE
CFC Mode: m
3
m
/h, cfm, l/s
K factor selection:
K FACTOR VALUE
RANGE: 1 to 1000
300
Maximum flow
rate selection.
MAX FLOW RATE
RANGE:
3
1000 m
/h
1 to 30.000
REF. FLOW RATE
SETPOINT selection:
RANGE: 1 to 30.000
3
500 m
/h
P VALUE
Proportional band selection:
RANGE: 0 to 20
180
Integral time selection:
VALUE I
RANGE: 0 to 10
4.00
WORK MODE
Min/Max
Unit of measure
selection:
UNITS OF
Min/Max Pa,
MEASURE
3
/s,
kPa, mbar, inWC
or mmWc
NOTE %:
MIN. VALUE
OUTPUT 0-10V
Motor
25%
RANGE: 0 to 100
NOTE %:
MAX. VALUE
OUTPUT 0-10V
Motor
80%
RANGE: 0 to 100

Werbung