Specification
High efficiency circulation pump
Δp = c (constant)
7
6
III
5
II
4
I
3
2
1
0
0
0,5
1,0
1,5
III
40
20
0
0
0,5
1,0
1,5
X Flow rate [m³/h]
Y Delivery head [m]
Z Power consumption [W]
WPKI-HKM E | WPKI-HK E
2,0
2,5
3,0
3,5
max.
3,5
2,0
2,5
3,0
7.2

Data table

Application limits
Max. permissible temperature
Max. permissible pressure
Hydraulic data
Flow capacity
Gravity brake opening pressure
Energy data
Energy Efficiency Index EEI
Versions
Circulation pump type
Dimensions
Height
Width
Depth
Connections
Connection above
Connection below
Values
Delivery head
Max. flow rate
7.3
Servomotor data table
Rated voltage
Connection
Rotational direction
Position indicator
Runtime
Safety category
IP rating
Ambient temperature
Test symbols
Guarantee
The guarantee conditions of our German companies do not
apply to appliances acquired outside of Germany. In countries
where our subsidiaries sell our products a guarantee can only
be issued by those subsidiaries. Such guarantee is only grant-
ed if the subsidiary has issued its own terms of guarantee. No
other guarantee will be granted.
We shall not provide any guarantee for appliances acquired in
countries where we have no subsidiary to sell our products.
This will not affect warranties issued by any importers.

Environment and recycling

We would ask you to help protect the environment. After use,
dispose of the various materials in accordance with national
regulations.
WPKI-HK E
WPKI-HKM E
233602
233603
°C
95
MPa
0.60
m³/h
7.20
MPa
0.02
0.20
Para 25-180/7-
Para 25-180/7-
50/SC-12
50/SC-12
mm
420
mm
250
mm
269
G 1
G 1 1/2 A
G 1 1/2 A
m
7.00
m³/h
3.30
230 V 50/60 Hz
cable 3 x 1.5 mm², 2 m long
optional acc. to wiring
reversible scale plate
140 sec
II (double insulated, without earth
conductor)
IP 40
0 °C to 50 °C
CE
95
0.60
5.80
0.02
0.20
420
250
269
G 1
7.00
3.30
| 11