internally (safe voltage) in the card and it is set in a way to guarantee the use of the double
insulation and reinforced in relation to parts with hazardous voltage.
- Any external circuits connected to the outputs of the control board, must be carried out to
make sure the double or reinforced insulation is used in relation to parts with hazardous
voltage.
- All the inputs are run by a programmed integrated circuit which carries out a self-check at
the beginning of each operation.
MAINTENANCE CHECK
N.B.: During this check the safety functions Edges, Photocells, Stop button and Impact
detection are NOT active.
1 - Set DIP 1 to ON => LED DL1 starts to flash.
2 - Press and hold the PROG button (the command is hold-to-run, open-stop-close-stop-open-
etc ...) => The gate starts at high speed and then slow down until the limit switch is reached.
3 - At the end, put DIP 1 back to OFF. The DL1 LED turn OFF signaling the exit from the check.
If the motor does not work during this check, check the connections and its capacitor.
If the motor is working properly, check the safety devices.
TROUBLE SHOOTING
After having carried out all connections, by carefully following the layout and having positioned
the gate in intermediate position, check the correct ignition of red LEDS DL6, DL7, DL8, DL9
and DL10.
In case of no ignition of the LEDS, always with gate in intermediate position, check the following
and replace any faulty components.
DL6
OFF Stop button malfunction (if Stop is not connected, perform the jump
between COM A+ and STOP).
DL7 or DL8
OFF Faulty photocells (In case the edge is not connected, carry out jumper
between COM A+ and PHOTO 1/PHOTO 2)
DL9 or DL10 OFF Faulty safety edge (In case the edge is not connected, carry out jumper
between COM A+ and EDGE 1/EDGE 2)
DL13 blue
ON
Some functions are enabled via smartphone, so via smartphone check the
card functions as the dips/trimmers status may not be true.
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable connectors and
insert them one at a time in order to more easily identify the cause of the fault.
After having carried out the various connections and having supplied voltage, all the LEDS are
switched OFF.
The motor opens and closes, but it has no strength and moves slowly.
The gate opens but does not close after the time set.
The gate does not open or close by activating the various START, RADIO, OPEN and CLOSE
buttons.
Motor with encoder (DIP 8 at On) enabled. The gate opens and closes only for brief intervals.
By activating the START, OPEN or CLOSE button the gate does not move.
The slowing phase is not performed.
FAULT
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable connectors and
insert them one at a time in order to more easily identify the cause of the fault.
Check the integrity of fuse F1.
In case of interrupted fuse use only of adequate value
F1 = T 5A Fuse for motor protection
Check trimmers TORQUE and LOW-SPEED adjustment.
Make sure that the TCA trimmer is activated with LED DL11 ON.
B.I.O. contact always on / green led on => check the status of the clock connected to B.I.O.
input.
Photocells Auto-test failed => check the connections between the control panel and the
photocells.
Faulty safety edge contact. Faulty photocells contact with DIP 4 OFF. => Fix or replace the
faulty contact.
Photocells Auto-test failed => check the connections between the control panel and the
photocells.
Check encoder connection and eventually replace.
START, OPEN or CLOSE command always active.
Check and replace any buttons or micro-switches of the selector switch.
Ensure that DIP 9 is ON (Slowdown enabled).
Perform the programming times procedure with DIP 2.
Check LOW SPEED trimmer adjustment.
26