Electrical Connections
Electrical Connections

SIDE VIEW

18.8mm 17.5mm
Digital Control
Module
(Height = 21.3mm)
N/C (Not Connected)
Mains Supply
Note:
D HP2000 or D HP10 required for commissioning.
Important installation information!
Installation and commissioning may only be done by an authorised
electrician. Mains power (230V~/50 Hz) to electrical equipment must
be switched off during installation. Applicable laws and standards of
the country in which the device is operated must be observed!
LightSpot Luminaire Controllers
D MSM2000D/DALI - Digital Control Module
D DHW / D DHS - Mini Detector Head
Mounting Details
The D MSM2000D/DALI Control Module is designed to be mounted
within the luminaire on fixing centres of 135mm. Connections to the
control module as shown above should be made using single-core
wire (0.5-1.5mm
).
2
The interconnect cable between the detector head and control
module should be routed away from the other luminaire internal
wiring and away from the lamp end-caps.
The recommended position for the detector is in the middle of the
luminaire. Where this is not possible and the sensor is fitted near
one end of the lamps, please ensure that the sensor is at the 'cold'
end of the lamps.
The D DHW / D DHS Mini Detector Head should be mounted such
that only the raised front section of the bezel protrudes through the
cut out in the louvre or infill panel. This should be constructed in
accordance with the dimensions above.
PEHA Lichtsteuerung – PEHA Elektro GmbH & Co. KG a Honeywell Company · Gartenstraße 49 · 58511 Lüdenscheid · Deutschland · www.peha.de · peha@peha.de

TOP VIEW

21.3mm
21.5mm
14.9mm
Polarity-free
}
Polarity-free
Digital Output
Digital Input
N
Neutral
}
Neutral
Polarity-free
Digital Output
1
OneSwitch Input
TM
OneSwitch Input
N/C
Neutral
N/C
Live
L
Live IN
Live IN
PE
N
L
OneSwitch Input
for manual control
32mm
21.5mm
Mini Detector
Head
Control Module Part No
Operating voltage 230V 50Hz 10%
+ -
MSM2000D
Control output: Digital
Max 4 x DSI or 2 x DALI Ballast
Digital Control Module
Power consumption: <2W
MSM2000D
tc 70 C
Operating voltage 230V 50Hz 10%
+ -
Please read instructions
Control output: Digital
MSM2000DALI
prior to installation
Max 4 x DSI Ballast
Made in the EC
Power consumption: <2W
Ex-Or Limited
Haydock Lane, Haydock
tc 70 C
Merseyside, WA11 9UJ
Read instructions prior to installation
Tel. 01942 719229
Made in the EC
Fax. 01942 272767
135mm
147.5mm
D MSM2000D
MSM2000D
}
Polarity-free
Polarity-free Digital Input
Digital Output
N
Neutral
Neutral
1
OneSwitch Input
TM
OneSwitch Input
N/C
N/C
L
Live IN
Live IN
Digital Regulating Ballast(s)
}
Polarity-free
Polarity-free
Digital Input
Digital Input
N
Neutral
Neutral
L
Live IN
Live IN
Installation Guidelines
1. The Mini Detector Head must be mounted within the luminaire.
Do not mount remotely.
2. The connecting cable must not be extended.
3. Artificial light illuminating the Mini Detector Head must only be
reflected from the room - i.e. there must be no direct illumination.
4. In order to receive satisfactory light-level regulating operation,
a detector must observe a substantially greater proportion of
artificial light from the luminaire(s) under its control than from
neighbouring luminaires not under its control. This is parti-
cularly important when planning the installed layout of linear
luminaires that have an integral detector positioned at one end.
5. Please read Application Note AN4015 for general advice on how
to optimise the installation of presence detectors intended for
light-level regulation.
Commissioning
Detectors are supplied factory pre-set which ensures the lighting
will switch on automatically as soon as power is applied. Final
commissioning of the detectors requires the use of the D HP2000
Programmer. Please refer to D HP2000 instructions for compre-
hensive commissioning instructions.
800mm
Flying Lead
RJ12
Plug
DHW/DHS
Detector
Connection
Connection
W4267C_DE_1204
Seite 5/7

Werbung

loading

Diese Anleitung auch für:

Peha d msm2000dali