Variablen-Tabelle für Produktversionen mit Luftkanalmontage
Function 04 Read Input Register
Register
Variable description
3x0001
CO2 Value Sampling 4s
3x0002
CO2 Value Sampling 32s
3x0003
RESERVED
3x0004
RESERVED
3x0005
Temperature Value Sampling 4s
3x0006
Temperature Value Sampling 32s
3x0007
Relative humidity Value Sampling 4s
3x0008
Relative humidity Value Sampling 32s
Function 05 Write Single Coil
Register
Variable description
0x0001
Reset (Auto zero) CO2
0x0002
RESERVED
0x0003
Automatic calibrationCO2
0x0004
RESERVED
0x0005
RESERVED
0x0006
RESERVED
0x0007
RESERVED
0x0008
RESERVED
0x0009
temperature measurement type
Function 06 Write Single Register & Function 16 Write Multiple Register
Register
Variable description
4x0023
Offset Temperature
4x0024
Offset Humidity
Function 08 Diagnostics
Sub Function Code
00
01
04
10
11
12
13
14
15
Function 17 Report Slave ID
Sub Function Code
00
01
02
03
04
05
06
(1)
: Schreibgeschützte Variablen, die über die Modbus-Überwachungssysteme auf den gewünschten Wert gesetzt werden
können, deren Wert aber nicht gelesen werden kann. In den CAREL-Überwachungsgeräten werden diese Variablen folglich im
Feld „Wert" mit den Symbolen „***" angezeigt, sofern sie nicht auf einen bestimmten neuen Wert gesetzt werden. In diesen Fällen
zeigt das Feld „Wert" bis zum nächsten Neustart die Nummer an, die bei der Programmierung an den Fühler gesendet wurde.
Sonde DP +030220661 rel. 2.3 - 2.3 - 06.12.2021
(1)
Parameter
Echo of transmission data (Loopback)
Restart Modbus (Reset listen-only mode)
Activation listen-only mode
Delete counter
Counter bus telegrams
Counter communication errors (Parity, CRC, frame errors, etc.) Unsigned 16 bit
Counter exception messages
Counter slave messages
Counter messages without answer
Parameter
Number of bytes
Slave ID (device type)
Slave ID (device class)
03 Status
04 Version number (release)
05 Version number (version)
06 Version number (index)
Saved
Data Type
Default
value
Signed 16 Bit
-
-
Signed 16 Bit
-
-
-
-
-
-
Signed 16 Bit
-
-
Signed 16 Bit
-
-
Signed 16 Bit
-
-
Signed 16 Bit
-
-
Saved
Data Type
Default
value
Bit 0
0
NO
-
-
Bit 2
0
YES
-
-
-
-
-
-
-
-
-
-
Bit 8
0
YES
(1)
Saved
Data Type
Default
value
Signed 10 Bit
0
YES
Signed 10 Bit
0
YES
Data Type
Unsigned 16 bit
Unsigned 16 bit
Unsigned 16 bit
Unsigned 16 bit
Data Type
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Min.
Max.
Min.
Max.
Value
value
range
range
350
5000
350
5000
350
5000
350
5000
-350
800
35C
+80C
-350
800
35C
+80C
0
1000
0
100%
0
1000
0
100%
Min.
Max.
Min.
Max.
Value
value
range
range
0
1
OFF
ON
0
1
OFF
ON
0
1
°C
°F
Min.
Max.
Min.
Max.
Value
value
range
range
-100
100
-10K
+10K
-100
100
-10%
+10%
ANSWER
Echo data
Echo message
No answer
Echo telegram
All valid bus messages
Faulty bus messages
Error counter
Slave messages
Broadcast messages (address 0)
ANSWER
6
AERSGARD® MODBUS
17 = T,H,V,P,C
18 = T,H,V,C
19 = T,H,C
20 = T,H
21 = T,H,P
T: temperature
H: relative humidity
V: air quality (VOC)
P: particulate matter (PM)
C: carbon dioxide (CO2)
60 = AERASGARD® / AERASREG®
255 = RUN, 0 = STOP
1...9
1...99
1
Tab. 3.h