Herunterladen Diese Seite drucken

Evon Smart Home Modul Light 1244-10 Inbetriebnahme

Lichtmodul
Verfügbare Sprachen

Verfügbare Sprachen

Modul Light 1244-10
:
Module dimensions
Evon Smart Home module type c (refer to technical data sheet
module types) width/height/depth: 67,5mm/85,0mm/70,0mm
Screw base depth 38,5mm Horizontal pitch [U] = 3,9 HU
Supply
Power supply
24 Vdc +/-10 %
Nominal consumption
2W
Overvoltage category
2
Duty cycle
100%
Environmental conditions
Operating conditions
-15..+55°C, 5..90 % rH, non-condensing
Storage conditions
-25..+70°C, 5..90 % rH, non-condensing
Pollution degree
2
Terminals
Terminal capacity
max. 2 x 1,5 mm2
Screws
Pozidrive 1 / Slot 4 x 0,8 mm
Tightening torque
0,4 Nm
Protection type (EN 60529)
IP 20
Tests/Certification
CE
Input
Type
Digital input
Type
Potential-free Digital input
Number
4
Terminals
T1..T4
Rated insulation voltage
250Vac
Input voltage
See Power supply
Level
<0,5 VDC = logic 0; >8 VDC = logic 1
Input resistance
min. 11.500 Ohm
Recommended circuit breaker
B13 (IEC/EN 60898-1)
Output
Type
Digital output
Sort
Potential-free relay contact, closer
Count
4
Terminals
L 1..4
Max. resistive loads
2300W
Incandescent or halogen lamps
2300W
(230V AC)
Halogen lamps with transformer
1800W
(6..24V)
LED lamps with EVG
1000W
LED lamps (230V AC)
500W
Fluorescent lamps with VVG
800W
Fluorescent lamps with EVG
1000W
Compact fluorescent lamps (CFL)
500W
Switching voltage AC
250V
Switching current AC (cosPhi = 1)
10A
Switching voltage DC
9..30V
Switching current DC (cosPhi = 1)
10A
Min. switching load
12V/100mA
*Changes and errors excepted. This document does not claim to be exhaustive. The terms and conditions apply to evon GmbH. For more Details please visit our website www.evon-smarthome.com
Intelligent lighting module for 4 light functions. With
integrated relays up to 10A.
ATTENTION ELECTRICAL VOLTAGE
Disconnect all system components from the mains before commencing work.
The components may ONLY cabled with the mains disconnected.
The cabling may only be carried out by trained expert personnel.
Important before commissioning:
• Supply every module with power. 

• Please check whether the GND supply corresponds to the earth zero potential. 

• Larger loads on the module outputs, together with capacitive and inductive loads, must be switched via relays. 

• The input channel may only be switched with 24 V DC. 

Wiring example:
Commissioning:
• Isolate the system from the mains before beginning commissioning. 

• Start the installation work with a controller (e.g. iX800) or a converter module
• The modules can only be mounted from left to right.
• Plug the included 5-pole smartCOM line connector into the left terminal of the
• Mount the module on the DIN rail; it will click when seated correctly.
• Push the module along the rail to the left-hand module in the system. Ensure that
• Please check whether the GND supply for the 24 V power supply corresponds to
• Once the power is switched on, the ON LED lights up green.

• The smartCOM LED flashes red.
S1200 on the left-hand side of the cabinet.
module. 

the free pins of the connector snap into place in the socket of the adjacent
module.
an earth zero potential!
Once the controller has recognized and addressed the modules, the smartCOM
red LED is extinguished and the allocation and configuration can begin via
visualization.
Notes:
• L/+12, L/+3 and L/+4 can be connected to different phase
• Larger loads on the module outputs, together with capacitive and inductive loads,
must be switched via relays.
• The input channel may only be switched with 24 V DC. Light inputs can be
configured for proximity sensors or switches.
• All channel switching functions are available and can be tested after installation.
• C12/C34 can be used to integrate switches with other potential levels.