Herunterladen Diese Seite drucken

Lingg & Janke eibDUO SECURE DIM4FU-2-FW Anleitung Seite 4

Vorschau ausblenden Andere Handbücher für eibDUO SECURE DIM4FU-2-FW:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

To enter the programming mode:
Set DIP 4 from OFF to ON
Set DIP 3 OFF for Leading-edge
Set DIP 3 ON for trailing-edge
DIP 1 OFF for setting the
minimum value.DIP 3 ON or
OFF
By KNX telegram is sent the
minimum value fixed by the test
button.
The dimmer channel just drives
back to zero.
DIP 1 ON for setting the
maximum value.
By KNX telegram is sent the
maximum value, fixed by the
test button.
The dimmer channel just drives
back to zero.
Set all DIP swiches to OFF.
The minimum and maximum
values are stored
Universal dimmer mode:
The dimmer starts in leading edge and switches
to the trailing edge if it detects that the load is
inductive and back into the leading edge, for a
capacitive load.
.
Energy saving lamps/ Trailing edge:
After powering it brings 1 minute 100% (warm-up
of the ESL). Afterwards he dims between the
programmed minimum and maximum value.
Energy saving lamps/ Leading edge:
After powering it brings 1 minute 100% (warm-up
of the ESL). Afterwards he dims between the
programmed minimum and maximum value.
LED-Lamps / Trailing edge 0 bis 100%
The dimmer drives in immediately to the required
value between 0 and 100% for retrofit LED and
incandescent lamps.
LED-Lamps / Trailing edge Min. to Maximum
value:
The dimmer drives in immediately to the required
value between min. and maximum value. For
retrofit LED and incandescent lamps.
LED-Lamps / Leading edge 0 bis 100%
The dimmer drives in immediately to the required
value between 0 and 100% for retrofit LED and
incandescent lamps.
LED-Lamps / Leading edge Min. to Maximum
value:
The dimmer drives in immediately to the required
value between min. and maximum value. For
retrofit LED and incandescent lamps.
By pressing the corresponding TEST
button on the power unit each channel
can be checked.
The first short push of the button, the
channel will go ON (memory)
With another long push dims down
the channel
With another press changes the
direction of dimming.
The test function is a top priority.
If the test function for 30 seconds is
not operated, then taken over again
the value of the interface.
If the interface does not provide value,
remains the key to the value set
(memory)
For maintenance the voltage must be
interrupted. (MCB)
All DIP-switches to ON.
Press test button
Power off
All DIP-switches to OFF.
Power on

Werbung

loading

Verwandte Produkte für Lingg & Janke eibDUO SECURE DIM4FU-2-FW

Diese Anleitung auch für:

Eibduo secure dim4fu-2-sec