Dimming Actuator
DIM4FU-2-FW
DIM4FU-2-SEC
The eibDUO 4-fold universal dimmers are suited for all
established dimmable types of lighting. The 4 separate
load terminals can be connectetd to 2.5 A loads each.
The control circuits automatically identify the load and
switch from leading-edge to trailing-edge control. Two
dimmer load terminals (A+B or C+D) can be connected in
parallel to allow a higher load.
For energy-saving lamps, standard bulbs ,Retrofit LED
lamps , mains voltage halogen lamps , low-voltage
halogen lamps with magnetic or electronic transformer
If necessary, the device can also be operated with
KNX-SECURE
max. group addresses
76
max. secure group keys
64
power supply
230V AC 45...65Hz
protection class
IP 20
dimensions
216 x 90 x 50 mm (12 RU*)
installation
35 mm DIN rail
operating temperature
-5 ... +40°C
max. start-up peak/channel 26 A
maximum load per channel 2.5A
Minimum load per channel 1W ohmic
power dissipation
at rated load
4.7W per channel
at standby
0.4W per channel
short-circuit protection
electronic instant shut-down
overload protection
temperature monitoring (75°C)
dimming technology
automatic leading/trailing
Edge detection
*RU = rail unit
- terminals L-L and N-N are wired internally
- terminal cross section: 0.08 - 2.5 mm²
- stripping lenght: 5 - 6 mm
- conductors permitted:
- single core
- multi-filar
- fine-wired, including tin-plated individual wires
- fine-wired, with wire end sleeves
DIM4FU-2-FW
ON DIP
ON DIP
LED
TEST
ON
TEST
ON
TEST
1 2 3 4
1 2 3 4
KNX
A
B
Prog
PE
N N L L LD
N N L L LD
N N L L LD
X X
X X
_ _
+ +
KNX
KNX
L1
L1
L2
L2
L3
L3
N N
PE
PE
- The LD load terminal is NOT galvanically
WARNINGS
isolated when the dimming actuator is switched
off. A separate automatic circuit breaker has to be
installed at the power supply.
! !
- Loads or parts thereof must NOT be added or
taken off during operation.
- When connecting two circuits in parallel the circuits have to be
connected to the same mains phase. When using two different mains
phases the dimmer will instantly be destroyed when connecting in
parallel Looping from load is forbidden.
- The maximum start-up peak is 26A. Exceeding this current,
especially with capacitive loads, the power unit will be destroyed.
- Channels A+B and C+D can be connected in parallel to allow higher
loads. Both circuits must have same mains phase and the ETS
parameters have to be set according to the parallel connection!
MANUAL OPERATION ONLY WITH UNPLUGGED BUS-TERMINAL!
The device must only be installed and configured by a qualified
professional!
If the outlets are connected to different mains phases which are not
protected by the same protector unit, a clearly visible note to that effect
has to be attached to the device!
Health and safety regulations have to be compiled with!
Do not open the device!
A faulty device must be returned immediately to Lingg & Janke OHG!
Programming the device is provided via the ETS
Software and the corresponding product data base.
The actual version is available at:
ON DIP
ON DIP
www.lingg-janke.de
ON
TEST
ON
1 2 3 4
1 2 3 4
in the service area
C
D
The functions required are assigned when setting the
parameters. During the planning phase with ETS,
N N L L LD
objects which are not assigned are not displayed either.
The application programm must always be fully
downloaded to the device, never partially. Partial
download of the programm may lead to malfunctions.
X X
KNX assoc. recommends removing the code sticker
from the device in secure mode.
The device is mounted on a DIN rail, DIN EN 60715
TH35
Position the device on the DIN rail from below. Apply
brief, strong pressure on the upper edge of the casing to
engage the casing with the rail.
The device can be removed from the rail without any
tools: simply slide it from the DIN rail upwards and
remove it from the top of the rail. Do not apply any force
lest the clamps be damaged.
To connect the wires to the screwless terminals, insert a
slotted screwdriver into the respective spring-clip button
of the terminal, which opens the terminal. Insert the wire
into the mounting hole and remove the screwdriver. The
wire is now locked in place.
At full rated load, every dimming actuator generates
heat loss. When the dimming actuator is installed in
a cabinet, care must be taken that the temparature of
the individual devices does not exceed 70°C.
Dokument Version 5.21