Door installation module
LM2
11039225
1. Description
Display module with 10 LEDs for 19" assembly frames. It is suitable
as alarm module in switch cabinet doors or remote control panels.
The individual LEDs are actuated by SNVT network variables.
METZ CONNECT | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-189
Distributed by RIA CONNECT GmbH and BTR NETCOM GmbH
Mounting instruction see www.metz-connect.com
2. Declaration of Conformity
The device was tested according to the applicable standards. Con-
formity was proofed. The declaration of conformity is available at
the manufacturer BTR NETCOM GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these
instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other countries
it applies to the equipment installer or the user to meet the
national directions.
Safety Instructions
Keep the applicable directions for industrial safety and prevention
of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation or
maintenance of the devices.
Only qualified personnel shall do mounting and installation work
with the devices, see section "qualified personnel".
The information of these instructions have to be read and
understood by every person using this device.
Symbols
Entwurf
Warning of dangerous electrical voltage
Danger
means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices and
whose professional qualification meets the requirements of their
work.
This includes for example:
• Qualification to connect the device according to the
preliminary
VDE specifications and the local regulations and a qualification to
put this device into operation, to power it down or to activate it
by respecting the internal directions.
• Knowledge of safety rules.
• Knowledge about application and use of the device within the
equipment system etc.
3. Technical Data
LON interface
Transceiver
TP/FT-10 free topology
Neuron
FT3120 , 4K EEPROM
Data format
Standard network variables (SNVT)
Transmission rate
78 kBit/s
Max. length
Line topology
2700 m / 64 nodes
free topology
500 m / 64 nodes
Cabling
Twisted Pair
Application software
XIF and NXE files are available as downloads at
www.metz-connect.com.
Supply
Operating voltage range
24 V DC ±15 %
Current consumption
53 mA
Duty cycle relative
100 %
Recovery time
500 ms
Housing
Dimensions WxHxD
1.575 x 5.067 x 1.378 in. (3UH; 8UL)
(40 x 128.7 x 35 mm)
Weight
66 g
Mounting position
any
Mounting
in 19" subassembly frame
as per IEC 297-3
accessories P/N 110361 or 110362
Material
housing
ABS
terminal blocks
polyamide 6.6 V0
Type of protection (IEC 60529)
housing
IP40
terminal blocks
IP20
Terminal Blocks
Supply and bus
max. AWG 16 (1.5 mm²) solid wire
max. AWG 18 (1.0 mm²) stranded wire
Wire diameter
0.012 up to max. 0.055 in.
(0.3 mm up to max. 1.4 mm)
Protective circuitry
polarity reversal protection
Temperature range
Operation
23° F to 131° F (-5 °C to +55 °C)
Storage
-4° F to +158° F (-20 °C to +70 °C)
Indication
10 LEDs
adjustable to yellow, red or green
If a LED is adjusted to yellow for acknowledgment (17.0 0) the
system will identify this as a maintenance signal and interprete it
accordingly at the LM1 module (annunciator module for message
collection). If a LED is adjusted to flash red, to acknowledge and to
unlock (52.5 0) this is identified as a failure message and interpreted
accordingly at the LM1 module.
4. Wiring
5. Mounting
Power down the equipment.
Installation
Electric installation and device termination shall be done by quali-
fied persons only, by respecting all applicable
specifications and regulations.
1. Remove the plastic sheath of the cable by 2.756 to 3.140 in.
(7 to 8 cm), then insert the cable into upper opening of the
mounting frame.
1
2
2. Mate the terminal block to the header on the rear of the first
module that is mounted in the 19" mounting frame. (The ter-
minal block is included to delivery for the LM1, for all other
modules it is available as accessory P/N ASP0250404).
3
4
3. Tighten the upper and lower screw of the module to the
mounting frame.
5
4. Strip the wires by 7 mm, (put a wire end sleeve on stranded
wires), insert the wire end into the terminal body and press
down the lever.
6