INSTALLATION
Reject water outlet connection: The reject water
is routed via the reject water hose, see fig. C(2),
to the reject water outlet. The hose may be
extended up to 4 m, and the minimum internal
diameter is 13 mm.
The connection is made to the water trap
via the dishwasher drain. If there is only a
reject water outlet spigot and this is already
connected, the intermediate section should
be changed to one with two spigots. The
reject water outlet spigot is placed before
the water trap. Affix the hose as shown in
fig. E, securely with the aid of one hose clip
and the bracket for the reject water hose.
The reject water hose should be placed
in a loop at least 50 mm and at most 500
mm above the top of the water purifier
and existing water trap using the
enclosed bracket.

Electrical connection

The water purifier should be connected to an
earthed electrical supply (230V, 50Hz and 10A).
We recommend connection using a plug, as some
operations require the power supply to be
temporarily interrupted. The plug should also be
easily accessible after installation.

Connecting the water purifier

Before the water purifier is placed in its intended
position, remove the three protective sleeves from
the water purifier's connections and the transport
protection under the pre-filter containers.
Feed water
1. Screw the feed water hose's bent end
onto the water purifier's connection. See
fig. F.
2. Open the shut-off valve on the feed and
check that there is no leakage at the
feed water hose.
Purified water
Connect the purified water hose from the
peripheral equipment to the water purifier.
See fig. F. Push the hose into the bottom
position, up to the mark (approx. 17 mm).
Use the angle bracket for the purified
water hose if the space behind the
appliance is limited.
Wastewater
The bent end of the reject water hose is
secured to the water purifier's reject water
connection using a hose clip. See fig. F.