Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 32
4.- Installation
The wiring between the detector/button and the station should NEVER be installed in a conduit together with
power, control or feeder cables.
WARNINGS
- The alarm and detectors should be installed in a place protected from vibrations, water and corrosive
gases, where the ambient temperature does not exceed the value indicated in the technical data.
The station should be installed in a place where the regular presence of people who can alert to the
presence of alarms is guaranteed.
- To prevent false alarms, the detector should be installed away from:
Ÿ
Maintenance rooms where solvents, paints or refrigerator gases are handled.
Ÿ
Fruit ripening or storage rooms, as some fruits can emit gases.
Smoke outlets located in confined spaces (carbon dioxide, propane, LPG) or from engines,
Ÿ
generators or motorised machinery (fork-lift trucks, etc.).
Ÿ
Particularly damp areas or with the risk of getting wet.
Ÿ
Areas with strong ventilation.
- Do not paint the detector or place it near solvents or paints.
- Neither the alarm or gas detector are suitable for areas classified as potentially explosive.

Station assembly

- Remove the cover T of the equipment (Fig. 1).
- Open the equipment and remove the front of the housing (Fig. 2).
- Drill the holes needed for the cable entry glands using the pre-stamped centres on the sides of the housing for
guidance.
- Drill 3 holes on the wall following the fixing holes 1, 2, 3. (Fig. 3).
- Fasten the glands into the equipment.
- Insert the 3 screws and wall plugs through the housing into the holes in the wall and tighten.
- Insert the cables through the glands.
- Fit the front of the housing (Fig.2).
- Connect the battery before closing the cover.
- Insert and tighten screws D, F (Fig. 1).
- Connect the cables as shown in the wiring diagram, close the cover T, insert and tighten screws A, C (Fig. 1).
FIG. 1
FIG. 2
15
222,1 mm
140 mm
FIG. 3

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis